1. If the stop valve of the oil circuit is closed or the feeding of oil is insufficient and the oil filter is blocked, it is necessary to check that the valve in the oil circuit is open, the oil filter works normally and clean the filter screen of the pump.
2. If the oil temperature is low, viscosity is too high or the temperature of the oil fed by pump is too high, the oil temperature needs to be increased or decreased.
3. If the the domestic sewage treatment equipment oil pump breaks down, the oil pump is required to be replaced.
4. If the bearing of fan motor is damaged, it is necessary to replace the motor or bearing.
5. If the fan impeller is too dirty, it is required to be cleaned.
The oil and air must be mixed for the combustion of the fuel droplets to take place. The combustion speed depends on the evaporation speed of oil droplets and the mixing speed of oil and air. The evaporation speed of oil droplets is related to the diameter and temperature of oil droplets. The smaller the fuel droplets, the higher the temperature and the faster the evaporation. On the other hand, it is conducive to mixing and combustion. The smaller the fuel droplets, the larger the air contract surface. Therefore, the fuel oil must be atomized before combustion. And, the oil can be heated and evaporated rapidly and fully burnt after it is injected to the furnace.
A process load is usually a high-pressure steam load. A process load pertains to manufacturing operations, where heat from steam or hot water is used in the process. A process load is further defined as either continuous or batch. In a continuous load, the demand is fairly constant - such as in a heating load. The batch load is characterized by short-term demands. The batch load is a key issue when selecting equipment, because a batch-type process load can have a very large instantaneous demand that can be several times larger than the rating of the boiler. For example, based on its size, a heating coil can consume a large amount of steam simply to fill and pressurize the coil. When designing a boiler room for a process load with instantaneous demand, a more careful boiler selection process should take place.
1. Your existing system is inefficient
Efficiency is key when it comes to plant heating. Utilizing efficient equipment can save your company a significant amount of money in the long run and it is better for the environment. If you know that your existing system is not as efficient as it could be and it is in need of repair, it may be worth looking into thermal oil system replacement.
2. Your existing system features helical coil technology
Helical coils are common in thermal oil heaters from most manufacturers. But there are many reasons why serpentine coils are the better way to go when it comes to thermal fluid heating. Repairs to helical coils can be so expensive and time consuming that in many cases you are better off investing in new equipment – and it is well worth it to consider a new thermal oil system that features serpentine coil technology instead.
In the case of a thermal oil heater in a high-temperature operation state, if it encounters an emergency situation of power failure, its correct treatment is:
When the circulating oil pump cannot operate normally due to power failure, the heat transfer oil in the furnace tube will exceed the allowable value in a short time due to the residual heat of the furnace. At this time, the cold oil switching valve should be opened to release the cold oil in the expansion tank. And sent to the oil storage tank. At the same time, wet coal pressure or emergency shutdown is required and needs to be completed within 5 minutes.
In addition, we need to pay attention to not to put the oil in the expansion tank clean, otherwise the system will inhale air and cause problems. An oil level mark can be made on the oil level of the oil storage tank. When the cold oil is replaced, the valve can be closed in time to avoid the expansion of the expansion tank and the oil storage tank.
ead below for our top three benefits to purchasing a low NOx heater for your facility.
They're Environmentally Friendly
When NO2 and NOx are released, they interact with other chemicals in the atmosphere that is harmful to the environment. The EPA has linked NOx emissions contributing to acid rain, smog, global warming, and smog. By using a low NOx heater, you greatly reduce NO2 pollution in the atmosphere.
Interested in decreasing waste and emissions? Learn why your facility needs a waste recovery unit.
They're Safer For Your Employees
According to the EPA, exposure to nitrogen oxides has been found to contribute to respiratory problems and diseases, like asthma. By installing a low NOx heater, you're potentially preventing damage to your employee's lungs.
They're More Efficient
As our low NOx heaters are built using a serpentine coil technology, they have space between the coil tubes which renders them 10 to 15% more efficient that hot oil heaters that feature helical coils.
The choice between a steam system or a thermal fluid system is governed by the process requirements. The range or process temperature is a deciding factor. If the system’s required temperature is above the freezing point of water (0°C) and below approximately 160°C, the choice is usually steam. However, if the required temperature is above 160°C, thermal fluid may be a better solution. Thermal oil heater systems can be designed with maximum operating temperatures to 325°C.
Yes, it is recommended to turn your boiler off whilst the tank is being filled and to leave it off for a short period afterwards of up to 30 minutes. This will ensure that any sediment that has settled on the base of your tank is not stirred up and drawn into your fuel line.