Few parameters critical to health of the Boiler are
(4)Heat rate of the Boiler. This is a composite index of many performance indicators. Most of them will appear below.
(5)Unburnt fuel in flue gas and at boiler bottom .
(6)Flue gas furnace exit temperature.
(7)Boiler tube metal temperatures.
(8)Oxygen in flue gas.
(9)Imbalances in flue gas temperature over a cross section.
(10)Spray water consumption in Super heater and Reheater.
(11)Heat radiation from insulation.
The above all affects the performance of the boiler.
The inlet gas pressure is different for different capacity boiler, for example, the pressure for 2 ton steam capacity boiler is about 8~10KPa, while for 4 ton steam capacity boiler is about 12~25KPa. You can tell us the boiler capacity you want, we will help you to get the gas inlet pressure.
The coal-fired boiler refers to the boiler uses various types of coal as fuel and converts the heat of coal to steam or hot water.
There are generally two calculation methods of the circulating water volume of a coal-fired hot water boiler. One is to calculate the hourly water volume of one square meter and the other is to calculate the design parameter volume of every ton. As for the make-up water volume of this type of boiler, it is usually calculated as 1% to 3% of its total circulating water.
The proximate analysis of coal is to dry, heat and burn coal samples as required to get the percentage of moisture, volatiles, fixed carbon and ash in the coal and learn about the characteristics of coal combustion.
If the final temperature of feed water doesn’t reach the saturated temperature after being heated by an economizer, (that is, the feed water has not reached the boiling state), we call the economizer as a nonsteaming economizer. Generally, the final temperature is 30-50℃ lower than the saturated temperature.
The dry bottom hopper is formed by bending the lower part of the water wall of the front and rear walls inward. The main function is to gather, cool and automatically discharge ash. It is also convenient for the connection and sealing of the lower header and the ash well.
Stack temperature is the temperature of the combustion gases (dry and water vapor) leaving the boiler. A well-designed boiler removes as much heat as possible from the combustion gases. Thus, lower stack temperature represents more effective heat transfer and lower heat loss up the stack. The stack temperature reflects the energy that did not transfer from the fuel to steam or hot water. Stack temperature is a visible indicator of boiler efficiency. Any time efficiency is guaranteed, predicted stack temperatures should be verified.
Stack loss is a measure of the amount of heat carried away by dry flue gases (unused heat) and the moisture loss (product of combustion), based on the fuel analysis of the specific fuel being used, moisture in the combustion air, etc.
The combustion air preheater is definitely one of heat exchanger applications. Based on Figure 1 below, flue gas simply leaves steam boiler and passes via air preheater. The combustion air is passed through this equipment too to increase its temperature before being combined with boiler fuel.
Because the temperature of combustion air is lower than the temperature of flue gas, combustion air receive heat transfer from flue gas through combustion air preheater in the process of convection heat transfer. The heat transfer make temperature of flue gas lower and consequently minimizes its heat loss and also decreases the air temperature to stack.