Boilers are often distinguished by fuels that power them. The kind of fuel makes an essential difference in operating costs and environmental impact, so it’s important to learn about the various types of boiler fuel.
Coal, is a common boiler fuel. It dominates the global energy arena due to its abundance, affordability and wide distribution across the world. The most commonly used coal fuels include anthracite, bituminous coal, sub-bituminous coal, lignite and peat.
Yes, it is recommended to turn your boiler off whilst the tank is being filled and to leave it off for a short period afterwards of up to 30 minutes. This will ensure that any sediment that has settled on the base of your tank is not stirred up and drawn into your fuel line.
1. In terms of boiler body structure, WNS series gas-fired (oil-fired) boilers are fire tube boilers; SZS series gas-fired (oil-fired) boilers are water tube boilers;
2. In terms of boiler working pressure, if the boiler pressure is below 1.6Mpa, the choice is usually the WNS series gas-fired (oil-fired) boiler, if the boiler pressure is above 1.6Mpa, the SZS series gas-fired (oil-fired) boiler may be a better solution. Some high-pressure boilers also adopted SZS series gas-fired (oil-fir...
The life of the heat medium oil for thermal oil heater is related to the operating temperature, and the life is shorter when the operating temperature is high.After half a year, the heat medium oil is used for sampling every 2-3 months. When the flash point of the heat medium oil changes by more than 20%, the acid value is less than 0.5 mgKOH/g, and the residual carbon is less than 1.5 wo/o, when the color of oil becomes dark, it indicates that it has failed and needed to be replaced.The relationship between heat transfer oil life and temperature is shown in the following table: (unit, year) 360℃ 360℃
360℃
360℃ 360℃ Neo SK-OIL 1400 10 Neo SK-OIL 1400 10 Neo SK-OIL 1400 =1 3-4 8-10 >10 KSK-OIL 280 1 3-4 6-8 >10
Specific performance:Low level alarm of expansion tank.Answer:Cause of failure:The pipeline system (including heater) has not been replenished in time after oil leakage or degassing. Troubleshooting:Eliminate system defects and add oil.
(Question details) Specific performance:Tube explosion and bulge of thermal fluid heater.Answer: Cause of failure:(1) Over temperature.(2) Over heating.(3) Hot oil metamorphism. Troubleshooting:(1) Emergency shutdown.(2) Oil discharge and fire extinguish.We use automatic control for operating, burning, high level tank level, outlet temperature and flowrate are all automatically regulated and protected to avoid overtemperature or overheating.