  • What is the process load of an industrial boiler? 2020-01-17
    A process load is usually a high-pressure steam load. A process load pertains to manufacturing operations, where heat from steam or hot water is used in the process. A process load is further defined as either continuous or batch. In a continuous load, the demand is fairly constant - such as in a heating load. The batch load is characterized by short-term demands. The batch load is a key issue when selecting equipment, because a batch-type process load can have a very large instantaneous demand that can be several times larger than the rating of the boiler. For example, based on its size, a heating coil can consume a large amount of steam simply to fill and pressurize the coil. When designing a boiler room for a process load with instantaneous demand, a more careful boiler selection process should take place.
  • What impact will flue gas passes have on boiler performance? 2020-01-10
    The number of passes that the flue gas travels before exiting the boiler has been a good criterion when comparing boilers. As the flue gas travels through the boiler it cools, and therefore changes volume. Multiple pass boilers increase efficiency because the passes are designed to maximize flue gas velocities as the flue gas cools. ZOZEN has developed new design technologies in our WNS series boilers allowing for comparable efficiencies in fewer passes, resulting in smaller boiler systems that will fit in tighter quarters.
  • What is the system load of an industrial boiler? 2020-01-10
    System load is measured in either BTUs or tons of steam (at a specific pressure and temperature). It would be nearly impossible to size and select a boiler(s) without knowing the system load requirements. Knowing the requirements leads to the following information: The boiler(s) capacity, taken from the maximum system load requirement. The boiler(s) turndown, taken from the minimum system load requirement. Conditions for maximum efficiency, taken from the average system load requirement. Determining the total system load requires an understanding of the type(s) of load in the system. There are three types of loads: heating, process, and combination.
  • What impact will excess air have on boiler performance? 2020-01-03
    Excess air provides safe operation above stoichiometric conditions. A burner is typically set up with 15% to 20% excess air in higher firing ranges. Higher excess air levels result in fuel being used to heat the air instead of transferring it to usable energy, increasing stack losses and significantly decreasing efficiency. Boilers with lower excess air throughout the operating range have higher efficiencies.
  • What impact will emissions have on boiler performance? 2019-12-27
    Emissions standards for boilers have become very stringent in many areas because of the new Clean Air regulations. The ability of the boiler to meet emissions regulations depends on the type of boiler and burner options. ZOZEN has options to meet 5ppm NOx regulations, as well as 1 ppm CO regulation at 30 ppm NOx out of the box. We can also custom-engineer Selective Catalytic Reduction (SCR) for more rigorous emissions controls.
  • What are condensing boilers? 2019-12-20
    Condensing boilers can achieve up to 98% thermal efficiency, compared to 70%-80% with conventional designs (based on the higher heating value of fuels). Typical models offer efficiencies over 90% when the return water temperature is at 110 ºF or less; the lower the return water temperature, the higher the efficiency gain.
  • What is the difference between steam and hot water boilers? 2019-12-20
    The primary purpose of the boiler is to supply energy to the facility's operations – for comfort heating, manufacturing process, laundry, kitchen, etc. The nature of the facility's operation will dictate whether a steam or hot water boiler should be used. Hot water is commonly used in heating applications, with the boiler supplying water to the system at 120°F to 220°F. The operating pressure for hot water heating systems usually is 30 psig to 125 psig (hydrostatic). Under these conditions, there is a wide range of hot water boiler products available. If system requirements are for hot water of more than 250°F, a high-temperature water boiler should be considered.
  • Why do you use low heat generation instead of high heat when calculating boiler thermal efficiency? 2019-12-13
    This is because, under normal circumstances, the exhaust temperature of the boiler cannot completely condense the water in the flue gas, and the difference between the low calorific value and the high calorific value is mainly in the part of the latent heat of vaporization, so the low heat is used. The value is calculated to reflect the true efficiency of the boiler. However, there will be some special circumstances. For example, if the boiler is a condensing boiler, the calculation of the condensed water portion should be calculated using the high calorific value.