(Question Details) Specific Performance:Broken coal is one of the most common failures of the coal feeder. The coal feeder is the lifeline of the boiler. Its normal operation is the basic guarantee for the normal and stable operation of the boiler, because it’s common occurrence that the coal feeder breaks the coal, especially when multiple coal feeders broken coal simultaneously, the improper handling resulting in overheating, explosion, coking, shutdown and other failures. Answer:cause of failure:(1) The particles of fluidized bed boiler fuel are coarse, but the fine particles in the fuel have a large amount of moisture. It is very easy to bond, resulting in the clogging of coal bunker and coal feeder.(2) Coal particles are jammed and squeezed in the coal feeder, causing the coal feeder chain to break.(3) Impurities in coal, such as woven bags and tree blocks, enter the coal feeder, causing coal feeders to jam, blockage, trip and break pins. Troubleshooting:(1) Fluidized Be
Question details (performance):The burner motor of the gas boiler is running and the ignition is normal, but it is stopped by failure. Answer: Fault reason:The solenoid valve is not opened because the solenoid valve coil is damaged or the cable is broken. Troubleshooting:Replace solenoid valve or fix circuit failure, check voltage on terminal.