1. In terms of boiler body structure, WNS series gas-fired (oil-fired) boilers are fire tube boilers; SZS series gas-fired (oil-fired) boilers are water tube boilers;
2. In terms of boiler working pressure, if the boiler pressure is below 1.6Mpa, the choice is usually the WNS series gas-fired (oil-fired) boiler, if the boiler pressure is above 1.6Mpa, the SZS series gas-fired (oil-fired) boiler may be a better solution. Some high-pressure boilers also adopted SZS series gas-fired (oil-fir...
The bed temperature rises sharply.
Oxygen levels go down and sometimes drop to zero.
The electric current of primary air fan is less and wind pressure of air compartment is higher.
Negative pressure of furnace is increased while the electric current of induced draft fan is reduced.
The slag discharge is difficult or unsuccessful.
When appearing bed clinkering, the bed temperature and bed pressure will be uneven distributed and not at normal condition; the measuring point of part bed tempe...
The air in the economizer and condenser has not drained yet when firing. The safety valves of economizer and condenser need to be turned on to exhaust steam. Return pipe valves also need to be turned on, enabling the steam in the economizer and condenser to return to softened water tank.
The outlet water temperature is so high that economizer and condenser will have vaporization phenomenon. The outlet water temperature of economizer and condenser need to be controlled.
The check valve of the...
For the selection of heat fluid boilers, first step is to determine several parameters: thermal power in the process, the oil temperature, and the use of waste heat.There are several methods for determining the boiler's thermal power:1. Calculation. According to the specific heat capacity of the material to be heated, the heating temperature difference, the processing amount per unit time, etc., the thermal power is equal to the product of the above three points, and the calculation result considers a certain margin amount as the boiler capacity.2. The sum of thermal power in the process equipment can also be used as the basis for the heat power.3. Refer to the experience of the same industry to increase or decrease on the basis of peers.4. If steam heating is used, it can be converted into heat transfer oil of the same tonnage and the capacity is appropriately reduced.The determination of the temperature of the heat transfer oil can be determined according to the characteristics of th
The life of the heat medium oil for thermal oil heater is related to the operating temperature, and the life is shorter when the operating temperature is high.After half a year, the heat medium oil is used for sampling every 2-3 months. When the flash point of the heat medium oil changes by more than 20%, the acid value is less than 0.5 mgKOH/g, and the residual carbon is less than 1.5 wo/o, when the color of oil becomes dark, it indicates that it has failed and needed to be replaced.The relationship between heat transfer oil life and temperature is shown in the following table: (unit, year) 360℃ 360℃
360℃
360℃ 360℃ Neo SK-OIL 1400 10 Neo SK-OIL 1400 10 Neo SK-OIL 1400 =1 3-4 8-10 >10 KSK-OIL 280 1 3-4 6-8 >10