All thermal fluids expand as they are heated. The amount of expansion is based on the operating temperature, system volume and the coefficient of thermal expansion of the fluid. An expansion tank must be provided to accommodate the increased system volume at operating temperature.
NOTE: All fluids expand at a different rate.
A typical system includes the heater, circulation pump, expansion tank, and the user's process. Depending on the temperature requirements and the system design control valves may also be utilized.
(Question details) Specific performance:The temperature difference between the inlet oil and the outlet oil temperature of the boiler exceeds the given value.Answer:Cause of failure:(1) The oil supply of the heat oil circulating pump is insufficient.(2) The boiler operates overload.(3) Thermal oil metamorphism.(4) The boiler does not match the heating equipment.(5) Bad insulation effect.(6) There is gas or steam in the thermal oil. Troubleshooting:(1) Remove the faults of oil pump and pipeline.(2) Operate at normal load.(3) Change new oil.(4) Choose proper boiler.(5) Check the insulation layer and repair the loopholes.(6) Remove air or steam. ZOZEN pays much attention to boiler furnace insulation also, the inside is made of high quality insulation material, external use of stainless steel plate, which can maximumly reduce heat loss and improve the operating environment.