Generally, there is moisture in heat medium oil. And, the moisture will be evaporated during the heating process of the oil. If the water vapor is not discharged from the thermal oil heater, it will cause the fluctuation of heat medium oil pressure. However, the oil-gas separator can separate the water vapor from the heat medium oil and discharge it from the heater, which ensures the stable oil pressure.
If the circulating pump of a thermal oil heater stops working suddenly. Then, some measures should be taken immediately to remove the fire source. If not, the stop of circulating pump will cause coking in the oil tube, which will shorten the service life of the heater.
1. The storage tank is used to store the heat medium oil of the heating system;
2. The storage tank is used to receive the overrunning heat medium oil;
3. The storage tank is used to supplement heat medium oil for the heating system;
4. The storage tank should be placed at the lowest position of the system;
5. A firewall should be placed between the storage tank and the thermal oil heater;
6. The storage tank should be operated at a low liquid level.
The selection of a burner of the gas-fired thermal oil heater should be determined according to the boiler proper structure and fuel characteristics and in combination with the actual conditions and requirements. In addition, this kind of boiler can adopt a waste heat recovery device to improve thermal efficiency and reduce heat energy loss.
Coal-fired boilers refer to boilers that use various kinds of coals as fuel and convert the heat value of coals to steam or hot water.
Some specific parameters should be provided to calculate the theoretical coal consumption of a set of 20 tph coal-fired boiler. If the rated steam pressure is 1 MPa, the heat value of coal is 7000 kcal / kg, the boiler inlet water temperature is 20 ° C, and the boiler thermal efficiency is 80%, the daily coal consumption is 50-56 tons.
The gas consumption of 10 tph gas-fired boiler is related to technical parameters.
Such as heating surface layout, heat preservation effect, heat loss, water capacity, etc. The calculation formula of gas consumption of 10 tph gas-fired boiler is as follows:
=10 tph gas-fired boiler output÷ thermal efficiency ÷calorific value of natural gas
= 6,000,000 kcal ÷ 0.98 ÷ 8,600 kcal / h = 712 m3
Therefore, the gas consumption of 10 tph gas-fired boiler is 712 m3/ h
The gas consumption of the above gas-fired boiler is calculated at full capacity. In practice, the gas consumption changes with the operation load and operation conditions. In addition, if thermal efficiency of the gas-fired boiler is different, the gas consumption is different, too. The higher thermal efficiency is, the lower gas consumption is.
The economizer is a heat exchanger equipment which utilizes heat recovery of flue gases to heat feedwater. It can increase boiler efficiency, reduce the temperature of flue gas and save the fuel by absorbing recovery of flue gases. Besides, the feedwater is heated through the economizer before it is supplied into steam drum to decrease the thermal stress of the steam drum wall caused by temperature difference, which can improve the operating conditions of steam drum and prolong the service life of the steam drum.
The term “boiler efficiency” is often substituted for thermal efficiency or fuel-to-steam efficiency. When the term “boiler efficiency” is used, it is important to know which type of efficiency is being represented. Why? Because thermal efficiency, which does not account for radiation and convection losses, is not an indication of the true boiler efficiency. Fuelto-steam efficiency, which does account for radiation and convection losses, is a true indication of overall boiler efficiency. The term “boiler efficiency” should be defined by the boiler manufacturer before it is used in any economic evaluation.