Generally, there is moisture in heat medium oil. And, the moisture will be evaporated during the heating process of the oil. If the water vapor is not discharged from the thermal oil heater, it will cause the fluctuation of heat medium oil pressure. However, the oil-gas separator can separate the water vapor from the heat medium oil and discharge it from the heater, which ensures the stable oil pressure.
If the circulating pump of a thermal oil heater stops working suddenly. Then, some measures should be taken immediately to remove the fire source. If not, the stop of circulating pump will cause coking in the oil tube, which will shorten the service life of the heater.
The gas consumption of 10 tph gas-fired boiler is related to technical parameters.
Such as heating surface layout, heat preservation effect, heat loss, water capacity, etc. The calculation formula of gas consumption of 10 tph gas-fired boiler is as follows:
=10 tph gas-fired boiler output÷ thermal efficiency ÷calorific value of natural gas
= 6,000,000 kcal ÷ 0.98 ÷ 8,600 kcal / h = 712 m3
Therefore, the gas consumption of 10 tph gas-fired boiler is 712 m3/ h
The gas consumption of the above gas-fired boiler is calculated at full capacity. In practice, the gas consumption changes with the operation load and operation conditions. In addition, if thermal efficiency of the gas-fired boiler is different, the gas consumption is different, too. The higher thermal efficiency is, the lower gas consumption is.
The economizer is a heat exchanger equipment which utilizes heat recovery of flue gases to heat feedwater. It can increase boiler efficiency, reduce the temperature of flue gas and save the fuel by absorbing recovery of flue gases. Besides, the feedwater is heated through the economizer before it is supplied into steam drum to decrease the thermal stress of the steam drum wall caused by temperature difference, which can improve the operating conditions of steam drum and prolong the service life of the steam drum.
The term “boiler efficiency” is often substituted for thermal efficiency or fuel-to-steam efficiency. When the term “boiler efficiency” is used, it is important to know which type of efficiency is being represented. Why? Because thermal efficiency, which does not account for radiation and convection losses, is not an indication of the true boiler efficiency. Fuelto-steam efficiency, which does account for radiation and convection losses, is a true indication of overall boiler efficiency. The term “boiler efficiency” should be defined by the boiler manufacturer before it is used in any economic evaluation.
This is because, under normal circumstances, the exhaust temperature of the boiler cannot completely condense the water in the flue gas, and the difference between the low calorific value and the high calorific value is mainly in the part of the latent heat of vaporization, so the low heat is used. The value is calculated to reflect the true efficiency of the boiler. However, there will be some special circumstances. For example, if the boiler is a condensing boiler, the calculation of the condensed water portion should be calculated using the high calorific value.
In the case of a thermal oil heater in a high-temperature operation state, if it encounters an emergency situation of power failure, its correct treatment is:
When the circulating oil pump cannot operate normally due to power failure, the heat transfer oil in the furnace tube will exceed the allowable value in a short time due to the residual heat of the furnace. At this time, the cold oil switching valve should be opened to release the cold oil in the expansion tank. And sent to the oil storage tank. At the same time, wet coal pressure or emergency shutdown is required and needs to be completed within 5 minutes.
In addition, we need to pay attention to not to put the oil in the expansion tank clean, otherwise the system will inhale air and cause problems. An oil level mark can be made on the oil level of the oil storage tank. When the cold oil is replaced, the valve can be closed in time to avoid the expansion of the expansion tank and the oil storage tank.
Efficiency is especially important on a large scale and manufacturing and production operations are no exception. Here are two key reasons why you may want to consider upgrading your industrial heating equipment or installing a new, highly efficient thermal fluid heating system in your plant or facility.