The boiler gas consumption calculation need the following parameters: gas calorific value and boiler thermal efficiency.
Theoretically, the gas consumption of boiler = boiler thermal capacity ÷ (calorific value of gas x boiler thermal efficiency )
Take the 1 tph steam boiler as an example:
= 600,000 cal / (8500Kcal * 0.98) =72m3/h, the 1 tph boiler's gas consumption per hour is about 72 cubic meters.
In a water tube steam boiler, unlike a fire tube, water circulates inside the tubes. The heat that is generated and the combustion gases that surround the tubes heat the water that circulates inside them. Many water-tube boilers operate according to the principle of natural water circulation.
The capacity of this type of boiler can be enhanced by increasing the number of tubes in the boiler.
The action of starting up a fire tube boiler for the first time is already a cold start. As a result, the mechanical load in this type of boiler is much greater, as the main characteristic of cold starts is the absence of boiling water and greater stress on the connection and anchorage elements of the boiler.
To make this start a bit easier for the boiler, the boiler operator should reduce the burner load to a boiling point.
In superheated industrial water boilers, the water is pressurized and boiled to 100°C producing steam. These boilers are pyrotubular, with a high volume of water and a large temperature exchange zone. The designs can adapt to temperatures and pressures according to needs.
Any boiler where the products of combustion flow on the inside of a tube with the heat transfer media (ex. water, steam, or hot oil) on the outside. The tubes can be orientated vertically, horizontally or at an angle.