Home Service FAQs FAQ of circulating fluidized bed boilers How to solve the problem of coking in circulating fluidized bed boiler operation?

How to solve the problem of coking in circulating fluidized bed boiler operation?

12 Jul 2018

(Question Details) Specific Performance:

(1) The bed temperature has risen sharply.

(2) The oxygen level drops even to zero.

(3) The current of the primary blower is reduced, and the wind pressure in the wind chamber is high and fluctuates.

(4) The furnace negative pressure increases and the induced draft fan current decreases.

(5) Difficulties in slagging.

(6) If coking in low temperature, the bed temperature, bed pressure distribution is uneven, the deviation is too large, the bed pressure, the plenum pressure, the bed temperature is not normal, and the local bed temperature measurement point is not normally raised or lowered.

(7) The bed pressure indicator value fluctuates little.

 

Answer: causes of failure :

(1) Improper operation, resulting in overheated bed temperature and coking.

(2) The primary air volume during operation is kept too small, which is lower than the minimum fluidized air volume, so that the material can’t be well fluidized but piled up, the temperature field of the entire furnace is changed, the burning share of the suspension stage is decreased, and the boiler output is reduced, if increase the amount of coal blindly at this time, it will inevitably cause overheating and coking.

(3) Bad fluidization caused by damaged hood.

(4) Recycling device blocking the ash and causing cycle interruption.

(5) The material pressure difference is too high.

 

Troubleshooting:

(1) Strengthen the combustion adjustment and increase the fluidization speed. If the material pressure difference is too high, the slag should be strengthened.

(2) If the bed temperature is too high, the coal supply will be reduced to zero,open the door with high negative pressure of the furnace, and remove the focal block with a hook.

(3) If the coking of furnace is serious, we should stop the operation of boiler.


Related FAQs View More
Related news View More
  • ZOZEN Boiler Expands African Footprint: High-Efficiency Coal-Fired Steam Boiler Dispatched to Zimbabwe
    Recently, at the modern production base of Wuxi ZOZEN Boiler Co., Ltd. (hereinafter referred to as "ZOZEN Boiler"), a set of SZL series coal-fired steam boiler has completed strict quality inspection and packaging processes and was officially loaded for shipment to Zimbabwe. As an export-oriented boiler manufacturer, ZOZEN Boiler's cooperation with a well-known Zimbabwean paper enterprise is not only a reflection of "Made in China" deepening its presence in the African market but also a testamen...
    03 Mar 2026
  • ZOZEN Boiler 2026 Sales Conference Successfully Held
    Spring brings new life and new beginnings. On February 25, 2026, the ninth day of the first lunar month—a date symbolizing longevity and good fortune—the "2026 ZOZEN Boiler Sales Conference & 2025 Annual Sales Awards Ceremony" was successfully held at the ZOZEN headquarters by Taihu Lake, Wuxi. The conference was themed "United We Start: Upholding Integrity with Innovation, Marching Towards Intelligence." General Manager Mr. Zhang Guoping, department heads, and the entire domest...
    25 Feb 2026
  • Guarding the Flavor of the "Red Industry": ZOZEN Gas Steam Boiler Solves Pain Points in Tomato Processing
    Every August to September, Xinjiang welcomes a grand feast of red harvest. As a globally significant production base for tomato paste, tomato products here are renowned for their high lycopene content. However, for tomato processing enterprises, this is not just a harvest season, but a race against time. The tomato maturity period is concentrated, and fresh fruit is difficult to store, leaving a processing window of only 45 to 55 days. Once equipment downtime occurs, mountains of fresh fruit wil...
    17 Feb 2026

Find the Right Boiler For You

Name *

Email *

WhatsApp/WeChat

Products

Power/Capacity