Home Service FAQs FAQ of circulating fluidized bed boilers How to solve the problem of coking in circulating fluidized bed boiler operation?

How to solve the problem of coking in circulating fluidized bed boiler operation?

12 Jul 2018

(Question Details) Specific Performance:

(1) The bed temperature has risen sharply.

(2) The oxygen level drops even to zero.

(3) The current of the primary blower is reduced, and the wind pressure in the wind chamber is high and fluctuates.

(4) The furnace negative pressure increases and the induced draft fan current decreases.

(5) Difficulties in slagging.

(6) If coking in low temperature, the bed temperature, bed pressure distribution is uneven, the deviation is too large, the bed pressure, the plenum pressure, the bed temperature is not normal, and the local bed temperature measurement point is not normally raised or lowered.

(7) The bed pressure indicator value fluctuates little.

 

Answer: causes of failure :

(1) Improper operation, resulting in overheated bed temperature and coking.

(2) The primary air volume during operation is kept too small, which is lower than the minimum fluidized air volume, so that the material can’t be well fluidized but piled up, the temperature field of the entire furnace is changed, the burning share of the suspension stage is decreased, and the boiler output is reduced, if increase the amount of coal blindly at this time, it will inevitably cause overheating and coking.

(3) Bad fluidization caused by damaged hood.

(4) Recycling device blocking the ash and causing cycle interruption.

(5) The material pressure difference is too high.

 

Troubleshooting:

(1) Strengthen the combustion adjustment and increase the fluidization speed. If the material pressure difference is too high, the slag should be strengthened.

(2) If the bed temperature is too high, the coal supply will be reduced to zero,open the door with high negative pressure of the furnace, and remove the focal block with a hook.

(3) If the coking of furnace is serious, we should stop the operation of boiler.


Related FAQs View More
Related news View More
  • Successful Application of ZOZEN Biomass Steam Boiler in Indonesia's Feed Industry
    Recently, PT PAKAN SEHAT UNGGUL, a prominent company in Indonesia's feed industry, selected ZOZEN Boiler's SZL series biomass steam boiler to provide efficient power for its production lines. This decision was based not only on ZOZEN Boiler's strong reputation in the Indonesian market but also on its expertise in the biomass energy sector.   Biomass Steam Boilers: A Key Role in Feed Production Biomass steam boilers play a critical role in feed production by providing a stable supply of h...
    18 Feb 2025
  • ZOZEN Thermal Oil Heaters Power Rongtai’s 100,000 Tons Green Production
    In the context of green transformation within the fine chemical industry, the stability and precision of thermal energy supply have become pivotal for both production efficiency and environmental performance. Anhui Rongtai New Materials Co., Ltd., with its annual production capacity of 100,000 tons of resin series, 85,000 tons of coating series, 20,000 tons of water-based UV electronic specialty materials, and 15,000 tons of water-based dispersion series products, has opted for ZOZEN Boiler&rsqu...
    11 Feb 2025
  • ZOZEN Boiler 2025 Sales Conference: Riding Against the Tide to Start a New Journey of High - Quality Development
    On February 6, 2025, Wuxi ZOZEN Boiler Co., Ltd. held its 2025 Annual Sales Conference with the theme of "Riding Against the Tide - Innovation and Change in the Era of Cut - throat Competition", as well as the 2024 Advanced Sales Commendation Ceremony. General Manager Zhang Guoping, middle - level managers, and sales elites gathered together to review the achievements of the past year and plan the development blueprint for the new year. Through experience sharing, strategic deployment, and comme...
    07 Feb 2025

Find the Right Boiler For You

Name *

Email *

WhatsApp/WeChat

Products

Power/Capacity