Home Service FAQs FAQ of circulating fluidized bed boilers How to solve the problem of coking in circulating fluidized bed boiler operation?

How to solve the problem of coking in circulating fluidized bed boiler operation?

12 Jul 2018

(Question Details) Specific Performance:

(1) The bed temperature has risen sharply.

(2) The oxygen level drops even to zero.

(3) The current of the primary blower is reduced, and the wind pressure in the wind chamber is high and fluctuates.

(4) The furnace negative pressure increases and the induced draft fan current decreases.

(5) Difficulties in slagging.

(6) If coking in low temperature, the bed temperature, bed pressure distribution is uneven, the deviation is too large, the bed pressure, the plenum pressure, the bed temperature is not normal, and the local bed temperature measurement point is not normally raised or lowered.

(7) The bed pressure indicator value fluctuates little.

 

Answer: causes of failure :

(1) Improper operation, resulting in overheated bed temperature and coking.

(2) The primary air volume during operation is kept too small, which is lower than the minimum fluidized air volume, so that the material can’t be well fluidized but piled up, the temperature field of the entire furnace is changed, the burning share of the suspension stage is decreased, and the boiler output is reduced, if increase the amount of coal blindly at this time, it will inevitably cause overheating and coking.

(3) Bad fluidization caused by damaged hood.

(4) Recycling device blocking the ash and causing cycle interruption.

(5) The material pressure difference is too high.

 

Troubleshooting:

(1) Strengthen the combustion adjustment and increase the fluidization speed. If the material pressure difference is too high, the slag should be strengthened.

(2) If the bed temperature is too high, the coal supply will be reduced to zero,open the door with high negative pressure of the furnace, and remove the focal block with a hook.

(3) If the coking of furnace is serious, we should stop the operation of boiler.


Related FAQs View More
Related news View More
  • ZOZEN Expands in Ecuador’s Paper Industry with Heavy Oil Steam Boiler Project
    ZOZEN Boiler has recently shipped a 10-ton WNS series heavy oil steam boiler to Ecuador, where it will support the production line of a local corrugated board packaging company. The project marks another step in ZOZEN’s expansion in Ecuador’s paper industry and reflects growing demand in South America for reliable steam supply, fuel adaptability, and after-sales support. ZOZEN WNS series heavy oil condensing steam boiler Stable steam supply matters in paper productionIn paper and...
    05 May 2026
  • ZOZEN Boiler to Exhibit at PALMEX JAKARTA 2026
    From May 6 to 7, 2026, ZOZEN Boiler will participate in Palmex Indonesia 2026 at Jakarta International Expo (JIEXPO), Indonesia. ZOZEN Boiler will welcome visitors at Booth 190 & 192. As an industry event focused on the palm oil sector in Southeast Asia, the exhibition brings together companies involved in palm oil processing, supporting energy systems, and industrial equipment, offering ZOZEN Boiler a valuable opportunity to meet customers from Indonesia and surrounding markets. ZOZEN Bo...
    28 Apr 2026
  • Bangladesh’s Textile Industry Continues to Grow, with Greater Focus on Fuel Adaptability and Operating Costs in Steam Boiler Configuration
    Bangladesh is one of the world’s major producers and exporters of garments and textiles. With a well-developed industrial chain covering textile, dyeing, printing, and garment manufacturing, long-term demand for industrial steam remains strong. In production processes such as dyeing, washing, drying, and finishing, steam boilers play an important role in ensuring stable heat supply. As local textile enterprises place greater emphasis on energy consumption control, fuel utilization, and ope...
    21 Apr 2026

Find the Right Boiler For You

Name *

Email *

WhatsApp/WeChat

Products

Power/Capacity