Home Service FAQs FAQ of circulating fluidized bed boilers Why the slag discharge tube of circulating fluidized bed boiler will be blocked?

Why the slag discharge tube of circulating fluidized bed boiler will be blocked?

12 Jul 2018

(Details on the problem) Specific Performance:

Slagging pipe blocks during operation of circulating fluidized bed boiler.

 

Answer:cause of failure:

(1) The internal shape is caused by the limited expansion of the wear-resistant material inside the slag discharge pipe. The internal components of the slag cooler are deformed, affecting the fluidization of the slag cooler; the slag cooler is deactivated for a long time or a single slag cooler is selected for slagging, and the bed material in the deactivated slag cooler is bonded under the influence of steam, which being low temperature coke.

(2) The operating personnel did not grasp the ratio of the fluidized air volume of the slag cooler. Inappropriate air volume ratio resulted in poor ash slag fluidization in the slag cooler.

 

Troubleshooting:

(1) Operation personnel should strengthen understanding of boiler operating conditions, adjust boiler parameters in a timely manner, set up the concept of boiler material dynamic balance, control boiler operating bed pressure at normal values, and try to avoid large boiler slag discharge.

(2) The slag cooler hood should be purged each time the boiler is stopped. It is found that the blocked hood must be opened to control the size of the fuel.

(3) Boiler slagging, slag cooler should be carried out alternately; the slag entering the slag cooler should be fully cooled to ensure the working conditions of slag cooler.

(4) Summarizing the experience of the fluidization air volume of the slag cooler, select the optimization parameters of the squid air volume in each plenum, including the lowest fluidization air volume of the slag cooler to ensure the normal fluidization of the slag cooler under any load.


Related FAQs View More
Related news View More
  • ZOZEN Boiler Facilitates Power Plant “Oil-to-Gas” Upgrade
    On March 20, 2025, the Guizhou Jinyuan Zhijin “Replacing Small Units with Large Ones” Relocation Project (2×660 MW), under State Power Investment Corporation, successfully achieved the first ignition of its boiler. This project replaced traditional oil-fired ignition fuel with liquefied natural gas (LNG), setting a new precedent for employing clean energy in 660 MW ultra-supercritical “W” flame boilers. As a key equipment supplier for this project, ZOZEN Boiler prov...
    15 Jul 2025
  • Building Bridges of Friendship: ZOZEN Boiler and Pakistan’s Textile Industry Forge Strong Partnerships
    Under the Belt and Road Initiative, economic and cultural ties between China and Pakistan are growing ever stronger, with more frequent exchanges between businesses from both countries. Recently, ZOZEN Boiler’s Sales Director led a team to visit Pakistan, where they held a meaningful meeting with Kohinoor Mills, a leading local textile company. During the gathering, both sides exchanged honorary plaques and thoughtful gifts—gestures that not only celebrate past collaborations but als...
    08 Jul 2025
  • ZOZEN Boiler Achieves Outstanding Results at Overseas Exhibitions in the First Half of 2025
    In the first half of 2025, as a leading enterprise in China’s industrial boiler sector, ZOZEN Boiler has actively expanded into global markets with an international vision and innovative drive. The company made impressive appearances at the Pakistan Textile Exhibition and the Russian HEAT&ELECTRO MACHINERY Expo, continuously expanding its brand influence and bringing efficient, environmentally friendly energy solutions to customers worldwide, contributing to the green upgrade of the in...
    01 Jul 2025

Find the Right Boiler For You

Name *

Email *

WhatsApp/WeChat

Products

Power/Capacity