  • What causes the explosion accident of the furnace of a gas-fired steam boiler 2020-05-08
    If the following three conditions occur during the burning and flame out process of a gas-fired boiler, the furnace is likely to blow up. 1.The residual gas content in the furnace reaches the ignition limit at the start-up phase of the furnace. 2.The fuel content in the furnace reaches the ignition limit after several times failure of ignition. 3.The fuel is sprayed out because of the halfway extinction of the flame. And, the temperature of the furnace can not meet the spontaneous combustion condition of the sprayed fuel. However, the content of the sprayed fuel reaches the ignition limit.
  • How to transform a coal fired boiler into a gas fired boiler 2020-05-01
    In the work of transforming a coal-fired boiler into a gas-fired boiler, the principle of changing the original boiler should be reduced without changing the pressure component of the boiler body. The transformation process should focus on the choice of gas burners, the determination of the number of burners, the layout of the burners, the matching design of the furnace layout, and the selection of explosion-proof measures. Step by step, both economic benefits and practicality should be considered.
  • What is the inlet pressure of a gas burner? 2020-05-01
    The inlet gas pressure is different for different capacity boiler, for example, the pressure for 2 ton steam capacity boiler is about 8~10KPa, while for 4 ton steam capacity boiler is about 12~25KPa. You can tell us the boiler capacity you want, we will help you to get the gas inlet pressure. 
  • What is the reason that causes flameout of a gas-fired boiler 2020-05-01
    1.Flamelifting caused by a sudden increase of gas pressure; 2.Gas supply disruptions caused by malfunction of solenoid valve; 3.Great gas constituent change and excessive moisture content.
  • What are the characteristics of gas-fired boilers? 2020-04-24
    1. The control system is equipped with a special computer controller, which makes the boiler running clear and easy to operate. 2. The burner is controlled by full-automatic program, and in case of failure, the burner stops automatically. 3. The boiler body is designed with reasonable structure, and the top is equipped with air vent. The boiler works under normal pressure and is far away from explosion danger. The full wet back three-way structure and corrugated tank design are adopted. The flue gas process is long, the temperature of exhaust gas is reduced, the heat transfer coefficient is increased, and the equipment life is prevented from being reduced due to the expansion and contraction of metal.
  • What is the oil ignition point of industrial boilers? 2020-04-03
    When the oil temperature rises to a certain temperature that the oil and gas molecules on the surface of the oil tend to saturate, can catch fire and maintain continuous combustion for a duration of not less than 5S. The temperature is called ignition point.
  • What are the maintenance contents of main systems of a gas-fired boiler? 2020-03-06
    Maintenance of the burner: thoroughly clean the rotor plate, ignition device, filter, oil pump, motor and impeller system, and add lubricant to the connecting rod device of air valve. Retest the combustion condition.
  • What is the standard gas consumption of 10 tph gas-fired steam boiler? 2020-02-21
    The gas consumption of 10 tph gas-fired boiler is related to technical parameters. Such as heating surface layout, heat preservation effect, heat loss, water capacity, etc. The calculation formula of gas consumption of 10 tph gas-fired boiler is as follows: =10 tph gas-fired boiler output÷ thermal efficiency ÷calorific value of natural gas = 6,000,000 kcal ÷ 0.98 ÷ 8,600 kcal / h = 712 m3 Therefore, the gas consumption of 10 tph gas-fired boiler is 712 m3/ h The gas consumption of the above gas-fired boiler is calculated at full capacity. In practice, the gas consumption changes with the operation load and operation conditions. In addition, if thermal efficiency of the gas-fired boiler is different, the gas consumption is different, too. The higher thermal efficiency is, the lower gas consumption is.