“boilers in food industry”- related faq

  • What function do thermal oil heaters have in kinds of industry? 2018-08-30
    Chemical industry: polymerization, condensation, distillation, rectification, concentration, evaporation, and melting.Petrochemical: synthesis, reaction, distillation, rectification, heating, heat preservation, storage tank heating, heavy oil heating.Oil grease: oil decomposition, deodorization, fatty acid distillation, heating, hydrogenation reaction, esterification.Plastic rubber: hot pressing, calendering, extrusion, vulcanization molding.Leather industry: artificial leather processing.Textile printing and dyeing: heat setting, drying, baking, evaporation, melting.Chemical fiber: polymerization, melt spinning, weaving machine processing, molding, thermosetting, stretching, drying.Paint: paint baking, drying, high temperature solid melting, home appliances, vehicle baking paint, painting.Automotive aircraft: painted baking, drying, thermoforming, high temperature bonding.Wood processing: hot pressing, drying, wood processing and wood products (materials, furniture), wood-based panels
  • What is the reason that the temperature difference between the inlet oil and the outlet oil in thermal oil heater exceeds the given value? 2018-07-12
    (Question details) Specific performance:The temperature difference between the inlet oil and the outlet oil temperature of the boiler exceeds the given value.Answer:Cause of failure:(1) The oil supply of the heat oil circulating pump is insufficient.(2) The boiler operates overload.(3) Thermal oil metamorphism.(4) The boiler does not match the heating equipment.(5) Bad insulation effect.(6) There is gas or steam in the thermal oil. Troubleshooting:(1) Remove the faults of oil pump and pipeline.(2) Operate at normal load.(3) Change new oil.(4) Choose proper boiler.(5) Check the insulation layer and repair the loopholes.(6) Remove air or steam. ZOZEN pays much attention to boiler furnace insulation also, the inside is made of high quality insulation material, external use of stainless steel plate, which can maximumly reduce heat loss and improve the operating environment.
  • What if tube explosion and bulge situation happen in the operation of thermal oil heater? 2018-07-12
    (Question details) Specific performance:Tube explosion and bulge of thermal fluid heater.Answer: Cause of failure:(1) Over temperature.(2) Over heating.(3) Hot oil metamorphism. Troubleshooting:(1) Emergency shutdown.(2) Oil discharge and fire extinguish.We use automatic control for operating, burning, high level tank level, outlet temperature and flowrate are all automatically regulated and protected to avoid overtemperature or overheating.
  • Why are the furnace tubes damaged in operation of coal-fired boilers? 2018-07-12
    (Question details) Specific performance:The wall thickness of several boiler tubes was significantly reduced in a large area, the remaining wall thickness was 2.0mm, and some furnace tubes were corroded and worn out. Furnace tube wall is covered with a thick layer of uneven scale, the surface of the scale is brick red and black, scale layer is loose, and it is easy to remove the inner wall of the furnace tube, after removing, the furnace tube wall covered with a layer of corrosion pits. There is a thin layer of brick red corrosion on the outer wall of boiler tube, some of which are attached with black adhesive. Answer: Fault reason:1. The boiler is seriously short of water.2. Poor water circulation and uneven combustion.3. The unqualified quality of the boiler water and undemanding chemical supervision make the inner wall of the pipe corrode and scale, causing the pipe overheat and reduction of the strength.4. Due to the presence of impurities and scale, the furnace tube is blocked ins
  • What causes the burner motor of the gas-fired boiler running and ignition is normal, but then stop by failure? 2018-07-12
    Question details (performance):The burner motor of the gas boiler is running and the ignition is normal, but it is stopped by failure. Answer: Fault reason:The solenoid valve is not opened because the solenoid valve coil is damaged or the cable is broken. Troubleshooting:Replace solenoid valve or fix circuit failure, check voltage on terminal.