In the adjustment of boiler operation, on the basis of ensuring safe operation, economic operation must also be achieved to improve boiler efficiency. In general boiler units, the efficiency can basically reach more than 92%, and the total loss is less than 8%. The loss is: exhaust heat loss, generally 5-6%, followed by mechanical incomplete combustion heat loss is less than 1-1.5 %, heat loss and ash slag physical heat loss are about 1%. (Physical heat loss for high ash coal ash residue will be greater).
From the point of view of quantification of indicators, the key to improving boiler efficiency is to reduce smoke loss and heat loss due to incomplete combustion of machinery. Pay attention to the flue gas temperature changes. Excessive flue gas temperature will affect the efficiency of the boiler. Too low temperature may cause low-temperature corrosion of the air preheater. Therefore, it is necessary to strengthen the adjustment according to the load changes during operation. When t
The fuel of a gas-fired boiler is gas such as natural gas, city gas, biogas and liquefied gas, etc. What kind of fuel the boiler burns is decided by an equipment called a burner. The boiler equipped with a gas-fired burner is called a gas-fired boiler. There are three methods of gas-fired boiler combustion as per technical characteristics of how the gas and air mix.
1. Diffusion combustion:
Gas and air mutually diffuse at the gas nozzle and are burning. The advantages are burning stably and with simple burner structure. However, the heated area is easy to be carbonized due to long flame, which is easy to produce incomplete combustion.
2. Premixed combustion:
A part of air and gas are premixed before combustion (coefficient of primary air surplus is between 0.2-0.8), and then being burned. The advantages are clear combustion flame, enhanced combustion, and high thermal efficiency.
It could also say, how much heat is required to rais the water temperature from 60 ℃ to 90 ℃.
To calculate heat required follow below steps
Q= mCp dt
Where
m - water flow rate (kg/hr)
Cp- specific heat of water
dt- temperature differences ( 90–60)
You will get heat required in kcal/ hr.
dividing to Q by fuel GCV and system efficiency you will come to know how much fuel (either it is coal or oil) required to raise the temperature of water from 60 ℃ to 90℃.
If the following three conditions occur during the burning and flame out process of a gas-fired boiler, the furnace is likely to blow up.
1.The residual gas content in the furnace reaches the ignition limit at the start-up phase of the furnace.
2.The fuel content in the furnace reaches the ignition limit after several times failure of ignition.
3.The fuel is sprayed out because of the halfway extinction of the flame. And, the temperature of the furnace can not meet the spontaneous combustion condition of the sprayed fuel. However, the content of the sprayed fuel reaches the ignition limit.
Coal-fired boilers refer to boilers that use various kinds of coals as fuel and convert the heat value of coals to steam or hot water.
Some specific parameters should be provided to calculate the theoretical coal consumption of a set of 20 tph coal-fired boiler. If the rated steam pressure is 1 MPa, the heat value of coal is 7000 kcal / kg, the boiler inlet water temperature is 20 ° C, and the boiler thermal efficiency is 80%, the daily coal consumption is 50-56 tons.
The temperature of flue gas generated by a biomass-fired boiler is relatively high. But it is not corrosive. So, it is suitable to use heat resisting glass fiber needled felt bag which has a good use effect. Moreover, this kind of cloth bag is not very expensive.
1. The fuel volume is 1 / 30 ~ 40 of the raw material volume after molding;
2. The specific gravity is 10-15 times of the raw material, and the moisture content is between 12% and 18% (the moisture content of coal is below 10-15);
3. The net calorific value can reach 3500-4500 kcal (the net calorific value of class II bituminous coal is 3700-4700 kcal / kg);
4. The ash content is less than 10% (the ash content of coal is more than 20%);
5. Volatile matter ≥ 65.62% (volatile matter of class II bituminous coal≥20%).
6. Biomass fuel belongs to renewable clean energy, which is the same as wind energy and solar energy. The biomass fuel is rich in resources, it can ensure the sustainable use of energy.
7. The sulfur content and nitrogen content of biomass fuel are low, the amount of SOx and NOx generated in the combustion process is low.