zozen boiler
HomeBoiler tagsDual fuel Hot Water generators

“Dual fuel Hot Water generators”- related faq

Tags list
  • What parameters are critical to the health of a coal-fired boiler? 2020-05-15
    Few parameters critical to health of the Boiler are (4)Heat rate of the Boiler. This is a composite index of many performance indicators. Most of them will appear below. (5)Unburnt fuel in flue gas and at boiler bottom . (6)Flue gas furnace exit temperature. (7)Boiler tube metal temperatures. (8)Oxygen in flue gas. (9)Imbalances in flue gas temperature over a cross section. (10)Spray water consumption in Super heater and Reheater. (11)Heat radiation from insulation. The above all affects the performance of the boiler.
  • What is the calculation method of the circulating water volume of a coal-fired hot water boiler? 2020-04-10
    The coal-fired boiler refers to the boiler uses various types of coal as fuel and converts the heat of coal to steam or hot water. There are generally two calculation methods of the circulating water volume of a coal-fired hot water boiler. One is to calculate the hourly water volume of one square meter and the other is to calculate the design parameter volume of every ton. As for the make-up water volume of this type of boiler, it is usually calculated as 1% to 3% of its total circulating water.
  • How is the dry bottom hopper formed in an industrial boiler? 2020-04-10
    The dry bottom hopper is formed by bending the lower part of the water wall of the front and rear walls inward. The main function is to gather, cool and automatically discharge ash. It is also convenient for the connection and sealing of the lower header and the ash well.
  • What is the theoretical daily coal consumption of a set of 20 tph coal-fired chain grate steam boiler 2020-03-13
    Coal-fired boilers refer to boilers that use various kinds of coals as fuel and convert the heat value of coals to steam or hot water. Some specific parameters should be provided to calculate the theoretical coal consumption of a set of 20 tph coal-fired boiler. If the rated steam pressure is 1 MPa, the heat value of coal is 7000 kcal / kg, the boiler inlet water temperature is 20 ° C, and the boiler thermal efficiency is 80%, the daily coal consumption is 50-56 tons.
  • What is the standard gas consumption of 10 tph gas-fired steam boiler? 2020-02-21
    The gas consumption of 10 tph gas-fired boiler is related to technical parameters. Such as heating surface layout, heat preservation effect, heat loss, water capacity, etc. The calculation formula of gas consumption of 10 tph gas-fired boiler is as follows: =10 tph gas-fired boiler output÷ thermal efficiency ÷calorific value of natural gas = 6,000,000 kcal ÷ 0.98 ÷ 8,600 kcal / h = 712 m3 Therefore, the gas consumption of 10 tph gas-fired boiler is 712 m3/ h The gas consumption of the above gas-fired boiler is calculated at full capacity. In practice, the gas consumption changes with the operation load and operation conditions. In addition, if thermal efficiency of the gas-fired boiler is different, the gas consumption is different, too. The higher thermal efficiency is, the lower gas consumption is.
  • Water for the boiler 2020-01-31
    A steam boiler plant must operate safely, with maximum combustion and heat transfer efficiency. To help achieve this and a long, low-maintenance life, the boiler water can be chemically treated. The operating objectives for steam boiler plant include: Safe operation. Maximum combustion and heat transfer efficiency. Minimum maintenance. Long working life. The quality of the water used to produce the steam in the boiler will have a profound effect on meeting these objectives.
  • Boiler water level alarms 2020-01-31
    The function of high and low level alarms. Low-level alarms will draw attention to low boiler water level and, if required, shut down the boiler. High-level alarms protect plant and processes. Where boilers are operated without constant supervision (which includes the majority of industrial boilers) low water level alarms are required to shut down the boiler in the event of a lack of water in the boiler. Low level may be caused by:
  • What is the process load of an industrial boiler? 2020-01-17
    A process load is usually a high-pressure steam load. A process load pertains to manufacturing operations, where heat from steam or hot water is used in the process. A process load is further defined as either continuous or batch. In a continuous load, the demand is fairly constant - such as in a heating load. The batch load is characterized by short-term demands. The batch load is a key issue when selecting equipment, because a batch-type process load can have a very large instantaneous demand that can be several times larger than the rating of the boiler. For example, based on its size, a heating coil can consume a large amount of steam simply to fill and pressurize the coil. When designing a boiler room for a process load with instantaneous demand, a more careful boiler selection process should take place.
1 2 3 4 5 6