zozen boiler
HomeBoiler tagsgas boilers south africa

“gas boilers south africa”- related faq

  • What is a fire tube boiler? 2019-05-31
    Any boiler where the products of combustion flow on the inside of a tube with the heat transfer media (ex. water, steam, or hot oil) on the outside. The tubes can be orientated vertically, horizontally or at an angle.
  • What conditions are required for the full combustion of biomass-fired boiler fuel on the chain grate? 2019-03-21
    1. Rational air distribution, supply sufficient and rational air by region; 2. Appropriate furnace temperature;3. Suitable air turbulence and mixing in furnace;4. Fuels remain long enough on chain grate and in the furnace;5. Keep a reasonable distance between the fuel hopper and the flame fronts to avoid igniting fuels in the hopper.The biomass-fired boilers are optimally designed according to the characteristics of different biomass fuels. ZOZEN will customize the biomass-fired boiler for ...
  • What's the difference between WNS series gas-fired (oil-fired) boilers and SZS series gas-fired (oil-fired) boilers? 2019-02-12
    1. In terms of boiler body structure, WNS series gas-fired (oil-fired) boilers are fire tube boilers; SZS series gas-fired (oil-fired) boilers are water tube boilers; 2. In terms of boiler working pressure, if the boiler pressure is below 1.6Mpa, the choice is usually the WNS series gas-fired (oil-fired) boiler, if the boiler pressure is above 1.6Mpa, the SZS series gas-fired (oil-fired) boiler may be a better solution.  Some high-pressure boilers also adopted SZS series gas-fired (oil-fir...
  • What are the causes of water attack in the economizer and condenser of a gas-fired boiler? 2018-11-23
    The air in the economizer and condenser has not drained yet when firing. The safety valves of economizer and condenser need to be turned on to exhaust steam. Return pipe valves also need to be turned on, enabling the steam in the economizer and condenser to return to softened water tank. The outlet water temperature is so high that economizer and condenser will have vaporization phenomenon. The outlet water temperature of economizer and condenser need to be controlled. The check valve of the...
  • What if combustion of biomass fuel boiler is not sufficient? 2018-07-12
    Question details (Specific performance):Biomass environmental protection and energy saving fuel made of straw and livestock etc., their combustion is not full. Answer: The cause of the problem:1. Air quantity is insufficient or too big.2. Outer flame position is not proper.Troubleshooting:1.Sufficient temperature: sufficient combustion of biomass boiler needs high temperature, combustion rate is proportional to the temperature, to raise the temperature as much as possible but guarantee there is no slagging.2. Proper air volume. If the air volume is too large, it will reduce the temperature of the furnace and increase the incomplete combustion of fuel. If the air volume is insufficient, the combustion efficiency will be reduced, and the waste of fuel will also increase the emission of smoke.3. Sufficient mixing of fuel and air. During the burning stage of biomass boilers, the sufficient mixing of air and fuel should be ensured and the disturbance should be strengthened during the burnin
  • What is the reason for the failure of the coal economizer pipe of the coal-fired boiler? 2018-07-12
    Question details (Performance):1. The furnace wall at the coal economizer leaks water and steam with abnormal sound.2. The water level in the boiler drops sharply, and the water supply is obviously greater than the evaporation capacity.3. Smoke exhaust temperature and water outlet temperature rise.Answer: Fault reason:1. The water quality does not reach standard, and the oxygen in the water is decomposed into corroded pipe walls when the temperature rises.2. The low feed water temperature and smoke exhaust temperature make the inner and outer wall of the coal economizer pipe produce acid corrosion, or flying ash wear the pipe wall thin. 3. The pipe is blocked by impurities, causing overheating.4. Poor materials, defects in manufacturing, installation and maintenance. Troubleshooting:1. When economizer is slightly broke, it still maintains boiler operation, and the gap seems will not expand rapidly, in this case, load operation should be reduced, and start the spare boiler immediately,
  • What is the reason for pump in the gas-fired boiler does not transfer oil? 2018-07-12
    Question details (performance):A pump in a gas boiler does not transfer oil. Answer: Fault reason:(1) Pump failure.(2) Oil pressure and power are reduced.(3) The oil inlet valve is not sealed.(4) The inlet pipe is not sealed.(5) The interceptor valve is closed.(6) The filter is contaminated.(7) The filter is not sealed.(8) The tubing is not sealed.(9) Pump suck air inlet.(10) The vacuum degree in oil tube is too high.Troubleshooting:(1) Replace with new pump.(2) Remove the inlet valve and clean or replace it.(3) Seal the inlet pipe.(4) Open.(5) Cleaning.(6) Replace the sealing ring.(7) Tighten and exhaust.(8) Clean the filter and valve.
  • What causes the burner motor of the gas-fired boiler running and ignition is normal, but then stop by failure? 2018-07-12
    Question details (performance):The burner motor of the gas boiler is running and the ignition is normal, but it is stopped by failure. Answer: Fault reason:The solenoid valve is not opened because the solenoid valve coil is damaged or the cable is broken. Troubleshooting:Replace solenoid valve or fix circuit failure, check voltage on terminal.