Home Service FAQs FAQ of coal-fired boilers What is the reason for the failure of the coal economizer pipe of the coal-fired boiler?

What is the reason for the failure of the coal economizer pipe of the coal-fired boiler?

12 Jul 2018

Question details (Performance):

1. The furnace wall at the coal economizer leaks water and steam with abnormal sound.

2. The water level in the boiler drops sharply, and the water supply is obviously greater than the evaporation capacity.

3. Smoke exhaust temperature and water outlet temperature rise.


Answer: Fault reason:

1. The water quality does not reach standard, and the oxygen in the water is decomposed into corroded pipe walls when the temperature rises.

2. The low feed water temperature and smoke exhaust temperature make the inner and outer wall of the coal economizer pipe produce acid corrosion, or flying ash wear the pipe wall thin.

3. The pipe is blocked by impurities, causing overheating.

4. Poor materials, defects in manufacturing, installation and maintenance.

 

Troubleshooting:

1. When economizer is slightly broke, it still maintains boiler operation, and the gap seems will not expand rapidly, in this case, load operation should be reduced, and start the spare boiler immediately, when standby boiler is in operation, then stop the boiler and repair.

2. When economizer is badly broken, insufficient filling water circulating pumps and pressure drops rapidly, in this case furnace should be emergent stopped, circulating water outlet flow should be reduced to keep boiler water pressure, keep the induced draft fan continues to run, stop boiler after remove furnace flue gas and steam.


Related FAQs View More
Related news View More
  • From Cartons to Films: ZOZEN Boiler Supports Stable Production in the Packaging Industry with Diverse Thermal Energy Solutions
    Packaging connects production with consumption. A carton, a piece of corrugated board, or a roll of plastic film may look light and simple, but behind each of them is a stable, continuous, and process-matched thermal energy system. As demand continues to grow in food packaging, industrial packaging, e-commerce packaging, and plastic packaging, the packaging industry is placing more specific requirements on boiler equipment: stable steam supply, fuel adaptability, process temperature control, ope...
    26 May 2026
  • ZOZEN Boiler’s Drouble Drum Biomass Boiler Debuts with a Renewed Exterior
    When an industrial boiler arrives on site, what first catches a customer’s attention is often not the specification sheet, but the overall appearance of the equipment in the plant environment. For boiler equipment, exterior design is not only about visual presentation; it also reflects the manufacturer’s approach to product details, on-site management, and brand image. ZOZEN Boiler has upgraded the exterior of its SZL series biomass boiler, presenting a more unified visual design and...
    19 May 2026
  • ZOZEN Boiler Concludes Its Participation at PALMEX JAKARTA 2026
    From May 6 to 7, 2026, PALMEX JAKARTA 2026, the International Palm Oil Industry Equipment Exhibition, was held at JIEXPO in Jakarta, Indonesia. At booths 190 & 192, ZOZEN Boiler presented its boiler products and thermal energy solutions for industries such as palm oil processing. During the two-day exhibition, ZOZEN welcomed multiple groups of visitors, including existing clients and new prospects. Some new visitors returned to the booth several times for further discussions, and the overall...
    12 May 2026

Find the Right Boiler For You

Name *

Email *

WhatsApp/WeChat

Products

Power/Capacity