“industrial boiler solutions”- related faq

  • What maintenance does a biomass boiler require? 2019-05-10
    We would recommend your biomass boiler has at least an annual maintenance service. Like anything if you maintain your boiler correctly it will last longer and perform better. Biomass boilers burning even the most difficult of materials can operate unattended, but weekly inspection visits are required to carry out a visual inspection of the boiler and fuel feed system, to check the lubrication of bearings and to empty the ashbin. As a large enterprise specializing in manufacturing boilers, ZOZEN...
  • When would I use steam versus hot water or thermal fluid? 2019-05-10
    Steam carries about 540 Kcal/kg of useful energy whereas hot water and thermal fluid carry much less energy. Steam does not require a pump to transfer the energy. Generally, if the heating temperatures required are <100°C, then hot water can be used and if temperatures >180°C are needed then thermal fluid might be a better choice. For process temperatures between 100°C and 180°C steam is considered a viable option.
  • Why is an expansion tank required? 2019-04-28
    All thermal fluids expand as they are heated. The amount of expansion is based on the operating temperature, system volume and the coefficient of thermal expansion of the fluid. An expansion tank must be provided to accommodate the increased system volume at operating temperature. NOTE: All fluids expand at a different rate.
  • What are the primary components of a thermal fluid system? 2019-04-22
    A typical system includes the heater, circulation pump, expansion tank, and the user's process. Depending on the temperature requirements and the system design control valves may also be utilized.
  • What are the phenomena of coking on the circulating fluidized bed boilers? 2018-11-23
    The bed temperature rises sharply. Oxygen levels go down and sometimes drop to zero. The electric current of primary air fan is less and wind pressure of air compartment is higher. Negative pressure of furnace is increased while the electric current of induced draft fan is reduced. The slag discharge is difficult or unsuccessful. When appearing bed clinkering, the bed temperature and bed pressure will be uneven distributed and not at normal condition; the measuring point of part bed tempe...
  • What function do thermal oil heaters have in kinds of industry? 2018-08-30
    Chemical industry: polymerization, condensation, distillation, rectification, concentration, evaporation, and melting.Petrochemical: synthesis, reaction, distillation, rectification, heating, heat preservation, storage tank heating, heavy oil heating.Oil grease: oil decomposition, deodorization, fatty acid distillation, heating, hydrogenation reaction, esterification.Plastic rubber: hot pressing, calendering, extrusion, vulcanization molding.Leather industry: artificial leather processing.Textile printing and dyeing: heat setting, drying, baking, evaporation, melting.Chemical fiber: polymerization, melt spinning, weaving machine processing, molding, thermosetting, stretching, drying.Paint: paint baking, drying, high temperature solid melting, home appliances, vehicle baking paint, painting.Automotive aircraft: painted baking, drying, thermoforming, high temperature bonding.Wood processing: hot pressing, drying, wood processing and wood products (materials, furniture), wood-based panels
  • What if combustion of biomass fuel boiler is not sufficient? 2018-07-12
    Question details (Specific performance):Biomass environmental protection and energy saving fuel made of straw and livestock etc., their combustion is not full. Answer: The cause of the problem:1. Air quantity is insufficient or too big.2. Outer flame position is not proper.Troubleshooting:1.Sufficient temperature: sufficient combustion of biomass boiler needs high temperature, combustion rate is proportional to the temperature, to raise the temperature as much as possible but guarantee there is no slagging.2. Proper air volume. If the air volume is too large, it will reduce the temperature of the furnace and increase the incomplete combustion of fuel. If the air volume is insufficient, the combustion efficiency will be reduced, and the waste of fuel will also increase the emission of smoke.3. Sufficient mixing of fuel and air. During the burning stage of biomass boilers, the sufficient mixing of air and fuel should be ensured and the disturbance should be strengthened during the burnin
  • How to solve the problem of coking in circulating fluidized bed boiler operation? 2018-07-12
    (Question Details) Specific Performance:(1) The bed temperature has risen sharply.(2) The oxygen level drops even to zero.(3) The current of the primary blower is reduced, and the wind pressure in the wind chamber is high and fluctuates.(4) The furnace negative pressure increases and the induced draft fan current decreases.(5) Difficulties in slagging.(6) If coking in low temperature, the bed temperature, bed pressure distribution is uneven, the deviation is too large, the bed pressure, the plenum pressure, the bed temperature is not normal, and the local bed temperature measurement point is not normally raised or lowered.(7) The bed pressure indicator value fluctuates little. Answer: causes of failure :(1) Improper operation, resulting in overheated bed temperature and coking.(2) The primary air volume during operation is kept too small, which is lower than the minimum fluidized air volume, so that the material can’t be well fluidized but piled up, the temperature field of the entire