“steam boilers south africa”- related faq

  • How do steam boilers work with biomass? 2019-06-06
    Biomass steam boilers recover the heat generated during the biomass combustion process to heat the water in the boiler exchanger circuit. The hot water is then diverted to the heating circuit. Occasionally it is necessary to remove the ashes generated by biomass combustion and clean the burner.  
  • What is a biomass boiler? 2019-04-19
    A biomass boiler is a boiler designed to burn solid fuels classed as biomass. Such boilers can be supplied to burn every form of biomass from woodchips, wood pellets or logs to waste agricultural materials such as straw and grain husks, olive kernels, rice and the dust from any of these including sawdust. Boilers need to be designed to burn specific materials, with any given boiler able to burn a limited range of biomass. ZOZEN biomass-fired boiler has wide fuel adaptability, is suitable for a wide variety of biomass fuels including biomass particle, wood chips, palm shell, straw and so on. The engineering technique personnel of ZOZEN optimized the design of the feeding hopper, the length and width of the fire grate, rotary speed of gearbox, 1st and 2nd air ratio, vapor orientation and position, etc; the above upgrades ensure the high thermal efficiency and stable operation of the boiler.
  • What conditions are required for the full combustion of biomass-fired boiler fuel on the chain grate? 2019-03-21
    1. Rational air distribution, supply sufficient and rational air by region; 2. Appropriate furnace temperature;3. Suitable air turbulence and mixing in furnace;4. Fuels remain long enough on chain grate and in the furnace;5. Keep a reasonable distance between the fuel hopper and the flame fronts to avoid igniting fuels in the hopper.The biomass-fired boilers are optimally designed according to the characteristics of different biomass fuels. ZOZEN will customize the biomass-fired boiler for ...
  • What are the causes of water attack in the economizer and condenser of a gas-fired boiler? 2018-11-23
    The air in the economizer and condenser has not drained yet when firing. The safety valves of economizer and condenser need to be turned on to exhaust steam. Return pipe valves also need to be turned on, enabling the steam in the economizer and condenser to return to softened water tank. The outlet water temperature is so high that economizer and condenser will have vaporization phenomenon. The outlet water temperature of economizer and condenser need to be controlled. The check valve of the...
  • Why does the biomass-fired boiler smoke in operation? 2018-07-12
    Question details (performance):Black smoke happens during operating. Answer: Fault reason:(1) Insufficient air volume, improper air distribution, low furnace temperature: boiler usually equipped with air preheater, but when the air preheater has leakage, hot air flow doesn't satisfy the need of burning, smoke will happen.(2) In the case of stalling situation in full automatic oil-fired boiler: significant increase of furnace negative pressure, no flame can be seen from the inspection hole, steam pressure and steam temperature drop, the steam flow decreases sharply. The water level drops suddenly and then rises sharply.(3) Incomplete fuel burning: this is the main cause of boiler smoke, in the operation, some combustible gases such as carbon monoxide, hydrogen, methane will be generated in addition to carbon dioxide, sulphur dioxide, water vapor and oxygen, nitrogen, etc. during incomplete combustion. They burn and generate black smoke. Incomplete combustion of fuel will not only lead t
  • How to solve the phenomenon of superheater explosion in circulating fluidized bed boiler operation? 2018-07-12
    (Question Details) Specific Performance:The pipe of superheater bursts in circulating fluidized bed boiler operation.The bed pressure indicator fluctuates little. Answer:  causes of failure:(1) Design Factors.(2) Manufacturing process, installation and maintenance quality.(3) The temperature control device is unreasonable or does not work properly.(4) Effect of operating conditions on overheating and explosion of superheater. Troubleshooting:(1) Report the fact to operator on duty and require operating the boiler in low load.(2) When the overheat damage is serious,please report it to operator on duty and require stoping the boiler immediately to prevent blowout of the near pipes.(3) Adjust the steam temperature as much as possible within the normal range.(4) If the superheater tube is not damaged badly, it has little effect on the temperature level of the steam, and it can be allowed to run in a low load range for a short period of time.
  • Why the slag discharge tube of circulating fluidized bed boiler will be blocked? 2018-07-12
    (Details on the problem) Specific Performance:Slagging pipe blocks during operation of circulating fluidized bed boiler. Answer:cause of failure:(1) The internal shape is caused by the limited expansion of the wear-resistant material inside the slag discharge pipe. The internal components of the slag cooler are deformed, affecting the fluidization of the slag cooler; the slag cooler is deactivated for a long time or a single slag cooler is selected for slagging, and the bed material in the deactivated slag cooler is bonded under the influence of steam, which being low temperature coke.(2) The operating personnel did not grasp the ratio of the fluidized air volume of the slag cooler. Inappropriate air volume ratio resulted in poor ash slag fluidization in the slag cooler. Troubleshooting:(1) Operation personnel should strengthen understanding of boiler operating conditions, adjust boiler parameters in a timely manner, set up the concept of boiler material dynamic balance, control boiler
  • Why are there percussive sounds and vibrations in the boiler drum or pipe of a coal-fired boiler? (water impact) 2018-07-12
    Question details (Performance):The steam pipe vibrates violently and has a dull impact sound.Answer:  fault reason: There is air in pipeline  ; automatic air vent valve is not turned on; or it is out of order. Troubleshooting: Check all the air release valves on the water supply pipe and the air release valves on the top of the boiler tube for gas storage. If the valve fails, it should be replaced immediately.