A process load is usually a high-pressure steam load. A process load pertains to manufacturing operations, where heat from steam or hot water is used in the process. A process load is further defined as either continuous or batch. In a continuous load, the demand is fairly constant - such as in a heating load. The batch load is characterized by short-term demands. The batch load is a key issue when selecting equipment, because a batch-type process load can have a very large instantaneous demand that can be several times larger than the rating of the boiler. For example, based on its size, a heating coil can consume a large amount of steam simply to fill and pressurize the coil. When designing a boiler room for a process load with instantaneous demand, a more careful boiler selection process should take place.
Loads vary, and a power plant must be capable of handling the minimum load, the maximum load, and any load variations. Boiler selection is often dictated by the variation in load demand, rather than by the total quantity of steam or hot water required. There are three basic types of load variations: seasonal, daily, and instantaneous.
The number of passes that the flue gas travels before exiting the boiler has been a good criterion when comparing boilers. As the flue gas travels through the boiler it cools, and therefore changes volume. Multiple pass boilers increase efficiency because the passes are designed to maximize flue gas velocities as the flue gas cools. ZOZEN has developed new design technologies in our WNS series boilers allowing for comparable efficiencies in fewer passes, resulting in smaller boiler systems that will fit in tighter quarters.
System load is measured in either BTUs or tons of steam (at a specific pressure and temperature). It would be nearly impossible to size and select a boiler(s) without knowing the system load requirements. Knowing the requirements leads to the following information:
The boiler(s) capacity, taken from the maximum system load requirement.
The boiler(s) turndown, taken from the minimum system load requirement.
Conditions for maximum efficiency, taken from the average system load requirement.
Determining the total system load requires an understanding of the type(s) of load in the system. There are three types of loads: heating, process, and combination.
Excess air provides safe operation above stoichiometric conditions. A burner is typically set up with 15% to 20% excess air in higher firing ranges. Higher excess air levels result in fuel being used to heat the air instead of transferring it to usable energy, increasing stack losses and significantly decreasing efficiency. Boilers with lower excess air throughout the operating range have higher efficiencies.
Emissions standards for boilers have become very stringent in many areas because of the new Clean Air regulations. The ability of the boiler to meet emissions regulations depends on the type of boiler and burner options. ZOZEN has options to meet 5ppm NOx regulations, as well as 1 ppm CO regulation at 30 ppm NOx out of the box. We can also custom-engineer Selective Catalytic Reduction (SCR) for more rigorous emissions controls.
Stack temperature is the temperature of the combustion gases (dry and water vapor) leaving the boiler. A well-designed boiler removes as much heat as possible from the combustion gases. Thus, lower stack temperature represents more effective heat transfer and lower heat loss up the stack. The stack temperature reflects the energy that did not transfer from the fuel to steam or hot water. Stack temperature is a visible indicator of boiler efficiency. Any time efficiency is guaranteed, predicted stack temperatures should be verified.
Stack loss is a measure of the amount of heat carried away by dry flue gases (unused heat) and the moisture loss (product of combustion), based on the fuel analysis of the specific fuel being used, moisture in the combustion air, etc.
Condensing boilers can achieve up to 98% thermal efficiency, compared to 70%-80% with conventional designs (based on the higher heating value of fuels). Typical models offer efficiencies over 90% when the return water temperature is at 110 ºF or less; the lower the return water temperature, the higher the efficiency gain.