The air in the economizer and condenser has not drained yet when firing. The safety valves of economizer and condenser need to be turned on to exhaust steam. Return pipe valves also need to be turned on, enabling the steam in the economizer and condenser to return to softened water tank.
The outlet water temperature is so high that economizer and condenser will have vaporization phenomenon. The outlet water temperature of economizer and condenser need to be controlled.
The check valve of the...
For the selection of heat fluid boilers, first step is to determine several parameters: thermal power in the process, the oil temperature, and the use of waste heat.There are several methods for determining the boiler's thermal power:1. Calculation. According to the specific heat capacity of the material to be heated, the heating temperature difference, the processing amount per unit time, etc., the thermal power is equal to the product of the above three points, and the calculation result considers a certain margin amount as the boiler capacity.2. The sum of thermal power in the process equipment can also be used as the basis for the heat power.3. Refer to the experience of the same industry to increase or decrease on the basis of peers.4. If steam heating is used, it can be converted into heat transfer oil of the same tonnage and the capacity is appropriately reduced.The determination of the temperature of the heat transfer oil can be determined according to the characteristics of th
(Question Details) Specific Performance:The pipe of superheater bursts in circulating fluidized bed boiler operation.The bed pressure indicator fluctuates little. Answer: causes of failure:(1) Design Factors.(2) Manufacturing process, installation and maintenance quality.(3) The temperature control device is unreasonable or does not work properly.(4) Effect of operating conditions on overheating and explosion of superheater. Troubleshooting:(1) Report the fact to operator on duty and require operating the boiler in low load.(2) When the overheat damage is serious,please report it to operator on duty and require stoping the boiler immediately to prevent blowout of the near pipes.(3) Adjust the steam temperature as much as possible within the normal range.(4) If the superheater tube is not damaged badly, it has little effect on the temperature level of the steam, and it can be allowed to run in a low load range for a short period of time.
Question details (Performance):1. The furnace wall at the coal economizer leaks water and steam with abnormal sound.2. The water level in the boiler drops sharply, and the water supply is obviously greater than the evaporation capacity.3. Smoke exhaust temperature and water outlet temperature rise.Answer: Fault reason:1. The water quality does not reach standard, and the oxygen in the water is decomposed into corroded pipe walls when the temperature rises.2. The low feed water temperature and smoke exhaust temperature make the inner and outer wall of the coal economizer pipe produce acid corrosion, or flying ash wear the pipe wall thin. 3. The pipe is blocked by impurities, causing overheating.4. Poor materials, defects in manufacturing, installation and maintenance. Troubleshooting:1. When economizer is slightly broke, it still maintains boiler operation, and the gap seems will not expand rapidly, in this case, load operation should be reduced, and start the spare boiler immediately,