1. The storage tank is used to store the heat medium oil of the heating system;
2. The storage tank is used to receive the overrunning heat medium oil;
3. The storage tank is used to supplement heat medium oil for the heating system;
4. The storage tank should be placed at the lowest position of the system;
5. A firewall should be placed between the storage tank and the thermal oil heater;
6. The storage tank should be operated at a low liquid level.
The selection of a burner of the gas-fired thermal oil heater should be determined according to the boiler proper structure and fuel characteristics and in combination with the actual conditions and requirements. In addition, this kind of boiler can adopt a waste heat recovery device to improve thermal efficiency and reduce heat energy loss.
Coal-fired boilers refer to boilers that use various kinds of coals as fuel and convert the heat value of coals to steam or hot water.
Some specific parameters should be provided to calculate the theoretical coal consumption of a set of 20 tph coal-fired boiler. If the rated steam pressure is 1 MPa, the heat value of coal is 7000 kcal / kg, the boiler inlet water temperature is 20 ° C, and the boiler thermal efficiency is 80%, the daily coal consumption is 50-56 tons.
The term “boiler efficiency” is often substituted for thermal efficiency or fuel-to-steam efficiency. When the term “boiler efficiency” is used, it is important to know which type of efficiency is being represented. Why? Because thermal efficiency, which does not account for radiation and convection losses, is not an indication of the true boiler efficiency. Fuelto-steam efficiency, which does account for radiation and convection losses, is a true indication of overall boiler efficiency. The term “boiler efficiency” should be defined by the boiler manufacturer before it is used in any economic evaluation.
Condensing boilers can achieve up to 98% thermal efficiency, compared to 70%-80% with conventional designs (based on the higher heating value of fuels). Typical models offer efficiencies over 90% when the return water temperature is at 110 ºF or less; the lower the return water temperature, the higher the efficiency gain.
This is because, under normal circumstances, the exhaust temperature of the boiler cannot completely condense the water in the flue gas, and the difference between the low calorific value and the high calorific value is mainly in the part of the latent heat of vaporization, so the low heat is used. The value is calculated to reflect the true efficiency of the boiler. However, there will be some special circumstances. For example, if the boiler is a condensing boiler, the calculation of the condensed water portion should be calculated using the high calorific value.
1. Your existing system is inefficient
Efficiency is key when it comes to plant heating. Utilizing efficient equipment can save your company a significant amount of money in the long run and it is better for the environment. If you know that your existing system is not as efficient as it could be and it is in need of repair, it may be worth looking into thermal oil system replacement.
2. Your existing system features helical coil technology
Helical coils are common in thermal oil heaters from most manufacturers. But there are many reasons why serpentine coils are the better way to go when it comes to thermal fluid heating. Repairs to helical coils can be so expensive and time consuming that in many cases you are better off investing in new equipment – and it is well worth it to consider a new thermal oil system that features serpentine coil technology instead.
In the case of a thermal oil heater in a high-temperature operation state, if it encounters an emergency situation of power failure, its correct treatment is:
When the circulating oil pump cannot operate normally due to power failure, the heat transfer oil in the furnace tube will exceed the allowable value in a short time due to the residual heat of the furnace. At this time, the cold oil switching valve should be opened to release the cold oil in the expansion tank. And sent to the oil storage tank. At the same time, wet coal pressure or emergency shutdown is required and needs to be completed within 5 minutes.
In addition, we need to pay attention to not to put the oil in the expansion tank clean, otherwise the system will inhale air and cause problems. An oil level mark can be made on the oil level of the oil storage tank. When the cold oil is replaced, the valve can be closed in time to avoid the expansion of the expansion tank and the oil storage tank.