Home Service FAQs FAQ of circulating fluidized bed boilers Why is the water wall tube damaged when the circulating fluidized bed boiler operates?

Why is the water wall tube damaged when the circulating fluidized bed boiler operates?

12 Jul 2018

(Question Details) Specific Performance:

(1) There are blasting sounds in the furnace, and the furnace chamber is under positive pressure. There is smoke emitted from the combustion chamber in a leakage. In severe cases, the explosion-proof door of the boiler body opens.

(2) Drum water level drops rapidly and the feedwater flow rate is not abnormally larger than steam flow. MFT acts when the water level is below -280mm.

(3) Drum pressure, steam flow rate, exhaust temperature decrease, smoke temperature difference increases on both sides.

(4) The negative pressure at the inlet of the flue and suction fan becomes smaller and the temperature difference between the two sides increased.

(5) Smoke temperature decreases at the inlet and outlet of the cyclone separator, and the temperature of the material returned is low.

(6) Bed pressure increases, bed materials clean, fluidization poof, bed temperature distributes unevenly and bottom slag discharge difficultly.

 

Answer:cause of failure:

(1) Fly ash wear thins the pipe wall.

(2) Defective membrane water wall.

 

Troubleshooting:

(1) If the water wall tube is not badly damaged and can maintain the normal position and the failure will not be expanded, the load can be appropriately reduced and the maintenance time can be shortened to run until the standby furnace is put into operation. If the standby furnace can’t be put into operation for a long time and the damage of the malfunctioning furnace is intensified, the furnace should be stopped immediately.

(2) If the normal water level cannot be maintained, stop the furnace immediately, stop the bottom material and circulating ash, keep the induced draft fan running, and stop the induced draft fan after the steam leakage is eliminated.

We are strictly in accordance with the provisions of the use of advanced automatic robot and welding machine to complete the manufacture of elbows and the welding between the elbow and flat steel, fully automated to ensure the accuracy of the distance between the two.


Related FAQs View More
Related news View More
  • A Boiler Generating Steam for Brewed Aroma: ZOZEN Boiler Supports Green Production at Yanjing Beer
    As the beer industry moves toward greener, more continuous, and more refined production, the steam system has become an important part of brewing operations. Recently, the cooperation case between ZOZEN Boiler and Yanjing Beer (Guilin Liquan) Co., Ltd. once again highlighted the essential role and system value of industrial boiler equipment in the food and beverage industry. Industrial Heat and Beer Brewing Are Closely Connected From a Drop of Beer, the Value of Stable Steam Becomes ClearYan...
    24 Jun 2026
  • ZOZEN Skid-Mounted Boiler Exported to Thailand Supporting a Stationery Manufacturer
    Recently, ZOZEN Boiler delivered a 3-ton WNS series skid-mounted steam boiler to a stationery products manufacturer in Thailand. The customer mainly produces solid glue, crayons, oil pastels and other stationery products. During production, the customer has clear requirements for continuous and stable steam supply. Based on the customer’s process features and site conditions, ZOZEN Boiler adopted a skid-mounted delivery solution, integrating the boiler body and auxiliary equipment to suppo...
    16 Jun 2026
  • ASME Certification Supports ZOZEN Boiler’s Biomass Gas-Fired Boiler Export to Brazil
    Brazil is an important sugarcane-producing country, with a mature sugarcane sugar industry chain and abundant bagasse resources. According to project information, Brazil produces more than 200 million tons of bagasse annually. How to convert bagasse from an agricultural by-product into a usable resource has become one of the focuses for local sugar producers. ZOZEN SZS Series Gas-Fired Steam Boiler Exported to Brazil The project supported by ZOZEN Boiler is the “CNBC500 Carbonization S...
    09 Jun 2026

Find the Right Boiler For You

Name *

Email *

WhatsApp/WeChat

Products

Power/Capacity