Why is the water wall tube damaged when the circulating fluidized bed boiler operates?
(Question Details) Specific Performance:
(1) There are blasting sounds in the furnace, and the furnace chamber is under positive pressure. There is smoke emitted from the combustion chamber in a leakage. In severe cases, the explosion-proof door of the boiler body opens.
(2) Drum water level drops rapidly and the feedwater flow rate is not abnormally larger than steam flow. MFT acts when the water level is below -280mm.
(3) Drum pressure, steam flow rate, exhaust temperature decrease, smoke temperature difference increases on both sides.
(4) The negative pressure at the inlet of the flue and suction fan becomes smaller and the temperature difference between the two sides increased.
(5) Smoke temperature decreases at the inlet and outlet of the cyclone separator, and the temperature of the material returned is low.
(6) Bed pressure increases, bed materials clean, fluidization poof, bed temperature distributes unevenly and bottom slag discharge difficultly.
Answer:cause of failure:
(1) Fly ash wear thins the pipe wall.
(2) Defective membrane water wall.
Troubleshooting:
(1) If the water wall tube is not badly damaged and can maintain the normal position and the failure will not be expanded, the load can be appropriately reduced and the maintenance time can be shortened to run until the standby furnace is put into operation. If the standby furnace can’t be put into operation for a long time and the damage of the malfunctioning furnace is intensified, the furnace should be stopped immediately.
(2) If the normal water level cannot be maintained, stop the furnace immediately, stop the bottom material and circulating ash, keep the induced draft fan running, and stop the induced draft fan after the steam leakage is eliminated.
We are strictly in accordance with the provisions of the use of advanced automatic robot and welding machine to complete the manufacture of elbows and the welding between the elbow and flat steel, fully automated to ensure the accuracy of the distance between the two.
-
DHX coal-fired CFB (circulating fluidized bed) steam boilerLive Chat20-75 t/h1.25-1.6 MPa
-
QXX coal-fired CFB (circulating fluidized bed) hot water boilerLive Chat14-58 MW1-1.25 MPa
-
DHL series coal-fired steam boilerLive Chat20-75 t/h1.25-5.4 MPa
-
Email us
-
WhatsApp: +86 18861589035
WeChat: +86 13506150756
Live Chat
-
Recently, PT PAKAN SEHAT UNGGUL, a prominent company in Indonesia's feed industry, selected ZOZEN Boiler's SZL series biomass steam boiler to provide efficient power for its production lines. This decision was based not only on ZOZEN Boiler's strong reputation in the Indonesian market but also on its expertise in the biomass energy sector. Biomass Steam Boilers: A Key Role in Feed Production Biomass steam boilers play a critical role in feed production by providing a stable supply of h...18 Feb 2025
-
In the context of green transformation within the fine chemical industry, the stability and precision of thermal energy supply have become pivotal for both production efficiency and environmental performance. Anhui Rongtai New Materials Co., Ltd., with its annual production capacity of 100,000 tons of resin series, 85,000 tons of coating series, 20,000 tons of water-based UV electronic specialty materials, and 15,000 tons of water-based dispersion series products, has opted for ZOZEN Boiler&rsqu...11 Feb 2025
-
On February 6, 2025, Wuxi ZOZEN Boiler Co., Ltd. held its 2025 Annual Sales Conference with the theme of "Riding Against the Tide - Innovation and Change in the Era of Cut - throat Competition", as well as the 2024 Advanced Sales Commendation Ceremony. General Manager Zhang Guoping, middle - level managers, and sales elites gathered together to review the achievements of the past year and plan the development blueprint for the new year. Through experience sharing, strategic deployment, and comme...07 Feb 2025