A cornertube boiler is a type of natural circulation water-tube boiler which differentiates itself from other water tube boilers by its characteristic water-steam cycle and a pre-separation of heated steam from the steam-water mixture occurs outside the drum and the unheated downcomers.
The heat requirements of the building materials manufacturing process are very varied. A steam boiler plays a key role in the process of creating building materials. For example, materials like molded brick rely very much on steam heat from an industrial steam boiler in order to pressurize and harden the elements that make up the brick. Without exposure to that kind of heat and pressure, these materials would be a loose construction of sediment, rather than dependable, solid building components....
Steam is very widely applied in the textile industry. It is commonly used in many subsectors and processes: manufacturing fabrics, manufacturing textile products…
The safety valve of the boiler refers to the valve on the top of the boiler near the boiler control room. The function of the safety valve is to be opened automatically to exhaust the steam and restore the pressure when the boiler pressure exceeds the specified valve, so as to ensure the safety of boiler pressure-bearing components and steam turbines.
The gas consumption of 10 tph gas-fired boiler is related to technical parameters.
Such as heating surface layout, heat preservation effect, heat loss, water capacity, etc. The calculation formula of gas consumption of 10 tph gas-fired boiler is as follows:
=10 tph gas-fired boiler output÷ thermal efficiency ÷calorific value of natural gas
= 6,000,000 kcal ÷ 0.98 ÷ 8,600 kcal / h = 712 m3
Therefore, the gas consumption of 10 tph gas-fired boiler is 712 m3/ h
The gas consumption of the above gas-fired boiler is calculated at full capacity. In practice, the gas consumption changes with the operation load and operation conditions. In addition, if thermal efficiency of the gas-fired boiler is different, the gas consumption is different, too. The higher thermal efficiency is, the lower gas consumption is.
Loads vary, and a power plant must be capable of handling the minimum load, the maximum load, and any load variations. Boiler selection is often dictated by the variation in load demand, rather than by the total quantity of steam or hot water required. There are three basic types of load variations: seasonal, daily, and instantaneous.
Economizer is one of steam boiler’s equipment which is used to heat feedwater before it is supplied into steam drum. Economizer is the heat exchanger equipment to increase boiler efficiency by absorbing heat recovery of flue gases. The lower temperature of flue gas out from stack, the heat loss will be less and the fuel which is needed to convert water into steam will be also less in certain circumstances. So it can be said that economizer can save the fuel efficiently. Economizer will make temperature of feedwater higher, so steam boiler can produce steam easily.