A typical system includes the heater, circulation pump, expansion tank, and the user's process. Depending on the temperature requirements and the system design control valves may also be utilized.
A biomass boiler is a boiler designed to burn solid fuels classed as biomass. Such boilers can be supplied to burn every form of biomass from woodchips, wood pellets or logs to waste agricultural materials such as straw and grain husks, olive kernels, rice and the dust from any of these including sawdust. Boilers need to be designed to burn specific materials, with any given boiler able to burn a limited range of biomass.
ZOZEN biomass-fired boiler has wide fuel adaptability, is suitable for a wide variety of biomass fuels including biomass particle, wood chips, palm shell, straw and so on. The engineering technique personnel of ZOZEN optimized the design of the feeding hopper, the length and width of the fire grate, rotary speed of gearbox, 1st and 2nd air ratio, vapor orientation and position, etc; the above upgrades ensure the high thermal efficiency and stable operation of the boiler.
A thermal fluid system is a closed loop using mineral or synthetic oil as the heat transfer fluid. These systems operate at elevated temperatures while maintaining low system pressures. Fluid is circulated within the heater tubes and flue gases heat the fluid.
1. Primary air fan: after being heated by the air pre-heater, primary air enters into the wind chamber, then into the furnace through wind caps through the air distributor to fluidize particulate materials;2. Secondary air fan: after being heated by the air pre-heater, secondary air enters into the furnace through the secondary air ducts for complete combustion of fuels; the seal air, conveying air and fuel spreading air of the feeding device also adopt secondary air; 3. Circ...
1. Rational air distribution, supply sufficient and rational air by region; 2. Appropriate furnace temperature;3. Suitable air turbulence and mixing in furnace;4. Fuels remain long enough on chain grate and in the furnace;5. Keep a reasonable distance between the fuel hopper and the flame fronts to avoid igniting fuels in the hopper.The biomass-fired boilers are optimally designed according to the characteristics of different biomass fuels. ZOZEN will customize the biomass-fired boiler for ...
1. In terms of boiler body structure, WNS series gas-fired (oil-fired) boilers are fire tube boilers; SZS series gas-fired (oil-fired) boilers are water tube boilers;
2. In terms of boiler working pressure, if the boiler pressure is below 1.6Mpa, the choice is usually the WNS series gas-fired (oil-fired) boiler, if the boiler pressure is above 1.6Mpa, the SZS series gas-fired (oil-fired) boiler may be a better solution. Some high-pressure boilers also adopted SZS series gas-fired (oil-fir...
The bed temperature rises sharply.
Oxygen levels go down and sometimes drop to zero.
The electric current of primary air fan is less and wind pressure of air compartment is higher.
Negative pressure of furnace is increased while the electric current of induced draft fan is reduced.
The slag discharge is difficult or unsuccessful.
When appearing bed clinkering, the bed temperature and bed pressure will be uneven distributed and not at normal condition; the measuring point of part bed tempe...
The air in the economizer and condenser has not drained yet when firing. The safety valves of economizer and condenser need to be turned on to exhaust steam. Return pipe valves also need to be turned on, enabling the steam in the economizer and condenser to return to softened water tank.
The outlet water temperature is so high that economizer and condenser will have vaporization phenomenon. The outlet water temperature of economizer and condenser need to be controlled.
The check valve of the...