  • When should use high-pressure versus low-pressure steam? 2019-05-23
    The pressure of the steam is directly related to its temperature. So process temperature will require steam used to be at a specified pressure. For example, a process requires that needs temperatures at 150°C will require steam delivered at 6 Kg/cm2 or higher.
  • When would I use steam versus hot water or thermal fluid? 2019-05-10
    Steam carries about 540 Kcal/kg of useful energy whereas hot water and thermal fluid carry much less energy. Steam does not require a pump to transfer the energy. Generally, if the heating temperatures required are <100°C, then hot water can be used and if temperatures >180°C are needed then thermal fluid might be a better choice. For process temperatures between 100°C and 180°C steam is considered a viable option.
  • What are the causes of water attack in the economizer and condenser of a gas-fired boiler? 2018-11-23
    The air in the economizer and condenser has not drained yet when firing. The safety valves of economizer and condenser need to be turned on to exhaust steam. Return pipe valves also need to be turned on, enabling the steam in the economizer and condenser to return to softened water tank. The outlet water temperature is so high that economizer and condenser will have vaporization phenomenon. The outlet water temperature of economizer and condenser need to be controlled. The check valve of the...
  • When should I replace the heat medium oil for thermal oil heater system? 2018-09-29
    The life of the heat medium oil for thermal oil heater is related to the operating temperature, and the life is shorter when the operating temperature is high.After half a year, the heat medium oil is used for sampling every 2-3 months. When the flash point of the heat medium oil changes by more than 20%, the acid value is less than 0.5 mgKOH/g, and the residual carbon is less than 1.5 wo/o, when the color of oil becomes dark, it indicates that it has failed and needed to be replaced.The relationship between heat transfer oil life and temperature is shown in the following table: (unit, year)  360℃ 360℃      360℃   360℃ 360℃   Neo SK-OIL 1400  10 Neo SK-OIL 1400  10 Neo SK-OIL 1400  =1 3-4 8-10 >10 KSK-OIL 280  1 3-4 6-8 >10
  • What is difference between thermal oil heaters and steam boilers? 2018-08-30
    1. They are all a heat conversion device. The heat transfer medium they use is different. The water used in the steam boiler is heated to become steam. The heat transfer medium of thermal oil heater is heat medium oil. The heat is transferred to the heated substance by the heat medium oil.2. When a higher heating temperature is required, such as 280 degrees, the steam pressure of the steam boiler should reach 7MPa or more, and the process piping and heat exchange equipment must also withstand the same pressure. The equipment cost is high and dangerous. Thermal oil heater provides a temperature above 280 degrees, but the pressure is lower than 1MPa.3. The temperature of thermal oil heater can be accurately controlled within 3 degrees and the temperature of the steam changes greatly.4. Thermal oil heater is used alone, the exhaust gas temperature is higher, and the thermal efficiency is lower than that of the steam boiler. However, if used in conjunction with a steam boiler, the
  • What is the reason that the temperature difference between the inlet oil and the outlet oil in thermal oil heater exceeds the given value? 2018-07-12
    (Question details) Specific performance:The temperature difference between the inlet oil and the outlet oil temperature of the boiler exceeds the given value.Answer:Cause of failure:(1) The oil supply of the heat oil circulating pump is insufficient.(2) The boiler operates overload.(3) Thermal oil metamorphism.(4) The boiler does not match the heating equipment.(5) Bad insulation effect.(6) There is gas or steam in the thermal oil. Troubleshooting:(1) Remove the faults of oil pump and pipeline.(2) Operate at normal load.(3) Change new oil.(4) Choose proper boiler.(5) Check the insulation layer and repair the loopholes.(6) Remove air or steam. ZOZEN pays much attention to boiler furnace insulation also, the inside is made of high quality insulation material, external use of stainless steel plate, which can maximumly reduce heat loss and improve the operating environment.