zozen boiler
HomeBoiler tagscentral heating boiler

“central heating boiler”- related faq

  • What is difference between thermal oil heaters and steam boilers? 2018-08-30
    1. They are all a heat conversion device. The heat transfer medium they use is different. The water used in the steam boiler is heated to become steam. The heat transfer medium of thermal oil heater is heat medium oil. The heat is transferred to the heated substance by the heat medium oil.2. When a higher heating temperature is required, such as 280 degrees, the steam pressure of the steam boiler should reach 7MPa or more, and the process piping and heat exchange equipment must also withstand the same pressure. The equipment cost is high and dangerous. Thermal oil heater provides a temperature above 280 degrees, but the pressure is lower than 1MPa.3. The temperature of thermal oil heater can be accurately controlled within 3 degrees and the temperature of the steam changes greatly.4. Thermal oil heater is used alone, the exhaust gas temperature is higher, and the thermal efficiency is lower than that of the steam boiler. However, if used in conjunction with a steam boiler, the
  • Why does the biomass-fired boiler smoke in operation? 2018-07-12
    Question details (performance):Black smoke happens during operating. Answer: Fault reason:(1) Insufficient air volume, improper air distribution, low furnace temperature: boiler usually equipped with air preheater, but when the air preheater has leakage, hot air flow doesn't satisfy the need of burning, smoke will happen.(2) In the case of stalling situation in full automatic oil-fired boiler: significant increase of furnace negative pressure, no flame can be seen from the inspection hole, steam pressure and steam temperature drop, the steam flow decreases sharply. The water level drops suddenly and then rises sharply.(3) Incomplete fuel burning: this is the main cause of boiler smoke, in the operation, some combustible gases such as carbon monoxide, hydrogen, methane will be generated in addition to carbon dioxide, sulphur dioxide, water vapor and oxygen, nitrogen, etc. during incomplete combustion. They burn and generate black smoke. Incomplete combustion of fuel will not only lead t
  • How to solve the phenomenon of superheater explosion in circulating fluidized bed boiler operation? 2018-07-12
    (Question Details) Specific Performance:The pipe of superheater bursts in circulating fluidized bed boiler operation.The bed pressure indicator fluctuates little. Answer:  causes of failure:(1) Design Factors.(2) Manufacturing process, installation and maintenance quality.(3) The temperature control device is unreasonable or does not work properly.(4) Effect of operating conditions on overheating and explosion of superheater. Troubleshooting:(1) Report the fact to operator on duty and require operating the boiler in low load.(2) When the overheat damage is serious,please report it to operator on duty and require stoping the boiler immediately to prevent blowout of the near pipes.(3) Adjust the steam temperature as much as possible within the normal range.(4) If the superheater tube is not damaged badly, it has little effect on the temperature level of the steam, and it can be allowed to run in a low load range for a short period of time.
  • Breakdown of Coal Feeding System during Operation of Circulating Fluidized Bed. 2018-07-12
    (Question Details) Specific Performance:Broken coal is one of the most common failures of the coal feeder. The coal feeder is the lifeline of the boiler. Its normal operation is the basic guarantee for the normal and stable operation of the boiler, because it’s common occurrence that the coal feeder breaks the coal, especially when multiple coal feeders broken coal simultaneously, the improper handling resulting in overheating, explosion, coking, shutdown and other failures. Answer:cause of failure:(1) The particles of fluidized bed boiler fuel are coarse, but the fine particles in the fuel have a large amount of moisture. It is very easy to bond, resulting in the clogging of coal bunker and coal feeder.(2) Coal particles are jammed and squeezed in the coal feeder, causing the coal feeder chain to break.(3) Impurities in coal, such as woven bags and tree blocks, enter the coal feeder, causing coal feeders to jam, blockage, trip and break pins. Troubleshooting:(1) Fluidized Be
  • What is the reason for the failure of the coal economizer pipe of the coal-fired boiler? 2018-07-12
    Question details (Performance):1. The furnace wall at the coal economizer leaks water and steam with abnormal sound.2. The water level in the boiler drops sharply, and the water supply is obviously greater than the evaporation capacity.3. Smoke exhaust temperature and water outlet temperature rise.Answer: Fault reason:1. The water quality does not reach standard, and the oxygen in the water is decomposed into corroded pipe walls when the temperature rises.2. The low feed water temperature and smoke exhaust temperature make the inner and outer wall of the coal economizer pipe produce acid corrosion, or flying ash wear the pipe wall thin. 3. The pipe is blocked by impurities, causing overheating.4. Poor materials, defects in manufacturing, installation and maintenance. Troubleshooting:1. When economizer is slightly broke, it still maintains boiler operation, and the gap seems will not expand rapidly, in this case, load operation should be reduced, and start the spare boiler immediately,
1 2 3 4 5 6 7