When regulating and controlling the coal-fired steam boiler, it will involve the banking-up operation which has a set of operating steps and points for attention. Strictly adhering to the operating steps will be helpful for the more efficient operation of coal-fired steam boiler and can extend its service life at the same time.
In the adjustment of boiler operation, on the basis of ensuring safe operation, economic operation must also be achieved to improve boiler efficiency. In general boiler units, the efficiency can basically reach more than 92%, and the total loss is less than 8%. The loss is: exhaust heat loss, generally 5-6%, followed by mechanical incomplete combustion heat loss is less than 1-1.5 %, heat loss and ash slag physical heat loss are about 1%. (Physical heat loss for high ash coal ash residue will be greater).
From the point of view of quantification of indicators, the key to improving boiler efficiency is to reduce smoke loss and heat loss due to incomplete combustion of machinery. Pay attention to the flue gas temperature changes. Excessive flue gas temperature will affect the efficiency of the boiler. Too low temperature may cause low-temperature corrosion of the air preheater. Therefore, it is necessary to strengthen the adjustment according to the load changes during operation. When t
Influencing factors of slagging on heating surface of boiler
(1) Ash characteristics of pulverized coal
Generally, the softening temperature ST of ash is used as the main indicator of slag formation. Coal with low ash melting point (ST<1200℃) is easy to slag. In addition, the slagging index also includes: silicon ratio, alkali-acid ratio, slagging index, limit viscosity and so on.
(2)Aerodynamic characteristics in the furnace
Improper air flow organization leads to flame center deviation, and the pulverized coal air flow flame adheres to the wall, causing local slagging of the water-cooled wall;
Improper air flow organization, forming flue gas retention vortex area and forming a reducing atmosphere (with CO), reducing the ash melting point and increasing the possibility of slagging.
Excess air coefficient: When the excess air in the furnace is too small, a reducing atmosphere may be generated, and the tendency of slagging will increase accordingly.
(3)Influence of boiler heat lo
The causes of coal erosion as distinct from all the other types of erosion are many but from a theoretical point of view are simply high velocity particles impacting and rubbing along the surface of the tubes.
The boiler designer minimises this by providing a volume in the furnace and a direction of travel of the coal such that it is burned before it can touch the tubes. This can be defeated by increasing the velocity reducing the combustibility or increasing the mass flow. All of these parameters occur if you reduce the calorific value of the fuel or overload the boiler. If you had no erosion before changing your fuel that is the cause. If you have never had design fuel you dont know if it would have eroded anyway. If it would the cause will be a different reason such as arodynamic flows and aiming of the burner or size of the tartget fireball centre. This is a serious problem and should be dealt with by an experienced expert.
It could also say, how much heat is required to rais the water temperature from 60 ℃ to 90 ℃.
To calculate heat required follow below steps
Q= mCp dt
Where
m - water flow rate (kg/hr)
Cp- specific heat of water
dt- temperature differences ( 90–60)
You will get heat required in kcal/ hr.
dividing to Q by fuel GCV and system efficiency you will come to know how much fuel (either it is coal or oil) required to raise the temperature of water from 60 ℃ to 90℃.
For same energy output when energy input is lesser efficiency increase. When maximum heat energy is generated from coal or losses in heat transfer are reduced efficiency increase. Coal in boulder size is burnt combustion may not be complete. There will be more unburnt coal. As per coal chemistry and as per boiler flue gas velocity as designed best coal size for full combustion is designed. Maximum crushed coal is also not the best. Then there will be more coal dust. According to general design in various technologies pulverized coal give best combustion for fbc boilers. For cfbc boilers generally crushed coal size is 6 mm.
When you achieve best combustion mean this is main contributor for increase in efficiency. Boiler design, heat transfer, flue gas velocity, heat losses, are other factors for efficiency.
In the work of transforming a coal-fired boiler into a gas-fired boiler, the principle of changing the original boiler should be reduced without changing the pressure component of the boiler body. The transformation process should focus on the choice of gas burners, the determination of the number of burners, the layout of the burners, the matching design of the furnace layout, and the selection of explosion-proof measures. Step by step, both economic benefits and practicality should be considered.
The proximate analysis of coal is to dry, heat and burn coal samples as required to get the percentage of moisture, volatiles, fixed carbon and ash in the coal and learn about the characteristics of coal combustion.