Black smoke in gas-fired boilers is typically an indication of incomplete combustion, where the fuel is not being burned efficiently. This can happen due to several reasons:
Poor Air-to-Fuel Ratio: The most common cause of black smoke is an improper balance between the air and fuel. Too much fuel or insufficient air leads to incomplete combustion, resulting in black smoke due to unburnt carbon particles.
Dirty or Clogged Burners: Over time, burners can become dirty or clogged, affecting the ef...
(Question details) specific performance:The gas boiler is powered on, press start, the motor does not turn. Answer: Fault reason:1. Insufficient pneumatic locking.2. The solenoid valve is not sealing, and there is air leakage at the joint. Check the lock.3. The thermal relay is open.4. At least one of the conditional circuits is not valid (water level, pressure, temperature and to check whether the program controller is energized to start). Troubleshooting:1. Adjust the air pressure to the requested value.2. Clean or repair solenoid valve pipe joint.3. Check whether the component is damaged and motor current by reset.4. Check whether the water level, pressure and temperature exceed the limit.ZOZEN gas-fired boiler adopts automatic control to control the operation, combustion, water level, temperature and steam pressure. In case of such problems, the system will automatically prompt the error code.
There are several ways to estimate the thermal efficiency of gas-fired boilers:
1. Direct method: This method involves measuring the amount of fuel consumed and the amount of heat produced by the boiler. By comparing these two values, it is possible to calculate the thermal efficiency of the boiler.
2. Indirect method: The indirect method involves measuring various parameters such as flue gas temperature, ambient air temperature, and fuel consumption, and then calculating the t...
Fuel-to-steam efficiency is a measure of the overall efficiency of the boiler. It accounts for the effectiveness of the heat exchanger as well as the radiation and convection losses. It is an indication of the true boiler efficiency and should be the efficiency used in economic evaluations. As prescribed by the ASME Power Test Code, PTC 4.1, the fuel-to-steam efficiency of a boiler can be determined by two methods: the InputOutput Method and the Heat Loss Method.
1. In terms of boiler body structure, WNS series gas-fired (oil-fired) boilers are fire tube boilers; SZS series gas-fired (oil-fired) boilers are water tube boilers;
2. In terms of boiler working pressure, if the boiler pressure is below 1.6Mpa, the choice is usually the WNS series gas-fired (oil-fired) boiler, if the boiler pressure is above 1.6Mpa, the SZS series gas-fired (oil-fired) boiler may be a better solution. Some high-pressure boilers also adopted SZS series gas-fired (oil-fir...
The air in the economizer and condenser has not drained yet when firing. The safety valves of economizer and condenser need to be turned on to exhaust steam. Return pipe valves also need to be turned on, enabling the steam in the economizer and condenser to return to softened water tank.
The outlet water temperature is so high that economizer and condenser will have vaporization phenomenon. The outlet water temperature of economizer and condenser need to be controlled.
The check valve of the...