Influencing factors of slagging on heating surface of boiler
(1) Ash characteristics of pulverized coal
Generally, the softening temperature ST of ash is used as the main indicator of slag formation. Coal with low ash melting point (ST<1200℃) is easy to slag. In addition, the slagging index also includes: silicon ratio, alkali-acid ratio, slagging index, limit viscosity and so on.
(2)Aerodynamic characteristics in the furnace
Improper air flow organization leads to flame center deviation, and the pulverized coal air flow flame adheres to the wall, causing local slagging of the water-cooled wall;
Improper air flow organization, forming flue gas retention vortex area and forming a reducing atmosphere (with CO), reducing the ash melting point and increasing the possibility of slagging.
Excess air coefficient: When the excess air in the furnace is too small, a reducing atmosphere may be generated, and the tendency of slagging will increase accordingly.
(3)Influence of boiler heat lo
1. During the start-up process of the burner, if the burner repeatedly alarms and locks, it should be found out the reason, find the fault and eliminate it, and then press the reset button to inherit the start. Note: The continuous press of the reset button should not exceed 10 seconds
2. If the burner is not successful in one combustion, the natural gas boiler induced draft fan should be restarted, and the second combustion can be started after 5 minutes of ventilation.
3. In the normal operation era, the burner close to the thermal equipment department (such as the connecting flange, etc.) will be very hot, to prevent the formation of burns. Do not place flammable materials in the vicinity to avoid causing fire.
4. During the operation of natural gas-fired boilers, it is necessary to closely supervise the working conditions of hot water circulation pumps and natural gas-fired boiler pressures, natural gas distribution bags, pipeline valves, pressure gauges, flow meters, and water
The fuel of a gas-fired boiler is gas such as natural gas, city gas, biogas and liquefied gas, etc. What kind of fuel the boiler burns is decided by an equipment called a burner. The boiler equipped with a gas-fired burner is called a gas-fired boiler. There are three methods of gas-fired boiler combustion as per technical characteristics of how the gas and air mix.
1. Diffusion combustion:
Gas and air mutually diffuse at the gas nozzle and are burning. The advantages are burning stably and with simple burner structure. However, the heated area is easy to be carbonized due to long flame, which is easy to produce incomplete combustion.
2. Premixed combustion:
A part of air and gas are premixed before combustion (coefficient of primary air surplus is between 0.2-0.8), and then being burned. The advantages are clear combustion flame, enhanced combustion, and high thermal efficiency.
The explosion-proof door of the gas-fired boiler is opened or broken when the combustible gas explosion suddenly increases the pressure, it then releases high-pressure gas to reduce the damage to the gas-fired boiler body and also ensure
The function of the gas-fired boiler explosion-proof door is usually reflected when the gas-fired boiler is ignited or running due to improper operation. For instance, the furnace is not purged before ignition, the furnace is still not purged even the ignition cannot successfully be lit, the nozzle is leaking, the fuel is not completely burned, and extinguished failure to cut off fuel quickly, etc. all of them may cause the furnace and tail flue to explode. Installing explosion-proof door for gas-fired boiler is to release the pressure to avoid the accident from expanding and also to ensure the safety of the industrial steam boiler when a slight explosion occurs in the furnace or flue.
The condensing boiler burns carbon-based fuel with oxygen in order to produce steam and carbon dioxide. The gases that escape this process (through a chimney) as exhaust are called flue gases. The major advantage is that they offer up to a 90% improvement in terms of efficiency when compared to standard gas boilers. Overall, condensing boilers are considered much more efficient in contrast to non-condensing gas boilers, a major consideration for any business running on a budget.
The characteristics of dust collector of coal-fired boiler:
1) Separating the particulate matters. The dust collector of coal-fired boiler can effectively separate the big particulate matters with ignition conditions, so as to reduce the obstruction of dust removal system and improve efficiency.
2) Reducing dust. The dust collector of coal-fired boiler can prevent the dust-contained gas from washing the bag to lower the dust concentration of dust-contained gas and extend the service life of filtering bag and pulse magnetic valve.
3) Adopting materials with high quality. The dust collector of coal-fired boiler adopts high-temperature resistant materials that can extend the service life of dust collector.
4) Adopting elastic piston ring. The mouth of filtering bag adopts elastic piston ring to ensure the leakproofness, which is firm and reliable.
There are many opinions on the best way to clean a steam boiler. One of the oldest ways is to dissolve a pound of tri-sodium phosphate (TSP) and a pound of caustic soda (lye) in water and pour it into the boiler. Let it cook for a few hours and then drain the boiler. If you can't buy TSP in your town, try a commercial soap called MEX. It works well and will not damage the rubber gaskets found in some boilers. However, before you clean any boiler, check the manufacturer's instructions for their recommendations.
For same energy output when energy input is lesser efficiency increase. When maximum heat energy is generated from coal or losses in heat transfer are reduced efficiency increase. Coal in boulder size is burnt combustion may not be complete. There will be more unburnt coal. As per coal chemistry and as per boiler flue gas velocity as designed best coal size for full combustion is designed. Maximum crushed coal is also not the best. Then there will be more coal dust. According to general design in various technologies pulverized coal give best combustion for fbc boilers. For cfbc boilers generally crushed coal size is 6 mm.
When you achieve best combustion mean this is main contributor for increase in efficiency. Boiler design, heat transfer, flue gas velocity, heat losses, are other factors for efficiency.