  • What is the reason that the temperature difference between the inlet oil and the outlet oil in thermal oil heater exceeds the given value? 2018-07-12
    (Question details) Specific performance:The temperature difference between the inlet oil and the outlet oil temperature of the boiler exceeds the given value.Answer:Cause of failure:(1) The oil supply of the heat oil circulating pump is insufficient.(2) The boiler operates overload.(3) Thermal oil metamorphism.(4) The boiler does not match the heating equipment.(5) Bad insulation effect.(6) There is gas or steam in the thermal oil. Troubleshooting:(1) Remove the faults of oil pump and pipeline.(2) Operate at normal load.(3) Change new oil.(4) Choose proper boiler.(5) Check the insulation layer and repair the loopholes.(6) Remove air or steam. ZOZEN pays much attention to boiler furnace insulation also, the inside is made of high quality insulation material, external use of stainless steel plate, which can maximumly reduce heat loss and improve the operating environment.
  • There is hammer sound, vibration and unstable pressure during the operation of thermal oil heater. 2018-07-12
    (Question details) Specific performance:There is hammer sound in the oil inlet pipe, and the pointer of the inlet and outlet pressure gauge fluctuates.Answers: Cause of failure:The system contains gas and moisture.Troubleshooting:(1) Exhaust air.(2) Cook oil.
  • Why are there percussive sounds and vibrations in the boiler drum or pipe of a coal-fired boiler? (water impact) 2018-07-12
    Question details (Performance):The steam pipe vibrates violently and has a dull impact sound.Answer:  fault reason: There is air in pipeline  ; automatic air vent valve is not turned on; or it is out of order. Troubleshooting: Check all the air release valves on the water supply pipe and the air release valves on the top of the boiler tube for gas storage. If the valve fails, it should be replaced immediately.
  • What causes the fan bearing to vibrate during boiler operation? 2018-07-12
    Question details (Performance):1. High temperature of motor, fast temperature rise.2. Overload, high outlet pressure and frequent safety valve open often.3. The vibration is intensified, the side vibration of the fan motor coupling is large, and the fan body never vibrates to vibration.4. No obvious vibration was found in no-load test of fan motor. Answer:  Fault reason:Fan bearing vibration is common fault in the operation, the vibration of the fan will cause damage of bearing and blade, bolt looseness, chassis and wind damage, fan vibration rises abruptly in the operation. this is because when the gas enter impeller and the rotating blade working face has certain angle, according to the principle of fluid mechanics, gas from non-working face must be a spiral blade, so the dust particles in the gas will slowly sedimentation due to vortex. Airfoil blades are very easy to accumulate dust. When the accumulated ash reaches a certain weight, a part of the large amount of accumulated ash wi
  • What is the reason for pump in the gas-fired boiler does not transfer oil? 2018-07-12
    Question details (performance):A pump in a gas boiler does not transfer oil. Answer: Fault reason:(1) Pump failure.(2) Oil pressure and power are reduced.(3) The oil inlet valve is not sealed.(4) The inlet pipe is not sealed.(5) The interceptor valve is closed.(6) The filter is contaminated.(7) The filter is not sealed.(8) The tubing is not sealed.(9) Pump suck air inlet.(10) The vacuum degree in oil tube is too high.Troubleshooting:(1) Replace with new pump.(2) Remove the inlet valve and clean or replace it.(3) Seal the inlet pipe.(4) Open.(5) Cleaning.(6) Replace the sealing ring.(7) Tighten and exhaust.(8) Clean the filter and valve.
  • What causes the burner motor of the gas-fired boiler running and ignition is normal, but then stop by failure? 2018-07-12
    Question details (performance):The burner motor of the gas boiler is running and the ignition is normal, but it is stopped by failure. Answer: Fault reason:The solenoid valve is not opened because the solenoid valve coil is damaged or the cable is broken. Troubleshooting:Replace solenoid valve or fix circuit failure, check voltage on terminal.