zozen boiler
HomeBoiler tagsnatural gas steam boiler high efficiency

“natural gas steam boiler high efficiency”- related faq

Tags list
  • What is the difference between steam and hot water boilers? 2019-12-20
    The primary purpose of the boiler is to supply energy to the facility's operations – for comfort heating, manufacturing process, laundry, kitchen, etc. The nature of the facility's operation will dictate whether a steam or hot water boiler should be used. Hot water is commonly used in heating applications, with the boiler supplying water to the system at 120°F to 220°F. The operating pressure for hot water heating systems usually is 30 psig to 125 psig (hydrostatic). Under these conditions, there is a wide range of hot water boiler products available. If system requirements are for hot water of more than 250°F, a high-temperature water boiler should be considered.
  • What is a fire tube steam boiler? 2019-07-05
    A fire tube steam boiler is a boiler where the combustion gases from the burner are channeled through tubes that are surrounded by the fluid to be heated. The boiler body is the pressure vessel and contains the fluid. In most cases, this fluid is water that will circulate for heating purposes or become steam for use in processing. Each set of tubes through which the combustion gas passes, before making a turn, is considered a "step". Consequently, a three-step boiler will have three sets of pipes with the outlet located at the rear of the boiler.
  • What are industrial boilers? 2019-06-21
    Industrial boilers are machines or engineering devices whose primary objective is the generation of steam. The heat that is generated, which can come from any energy source, causes it to be transformed into energy for use, either through a liquid phase medium or steam.
  • How do steam boilers work with biomass? 2019-06-06
    Biomass steam boilers recover the heat generated during the biomass combustion process to heat the water in the boiler exchanger circuit. The hot water is then diverted to the heating circuit. Occasionally it is necessary to remove the ashes generated by biomass combustion and clean the burner.  
  • What are the causes of water attack in the economizer and condenser of a gas-fired boiler? 2018-11-23
    The air in the economizer and condenser has not drained yet when firing. The safety valves of economizer and condenser need to be turned on to exhaust steam. Return pipe valves also need to be turned on, enabling the steam in the economizer and condenser to return to softened water tank. The outlet water temperature is so high that economizer and condenser will have vaporization phenomenon. The outlet water temperature of economizer and condenser need to be controlled. The check valve of the...
  • What function do thermal oil heaters have in kinds of industry? 2018-08-30
    Chemical industry: polymerization, condensation, distillation, rectification, concentration, evaporation, and melting.Petrochemical: synthesis, reaction, distillation, rectification, heating, heat preservation, storage tank heating, heavy oil heating.Oil grease: oil decomposition, deodorization, fatty acid distillation, heating, hydrogenation reaction, esterification.Plastic rubber: hot pressing, calendering, extrusion, vulcanization molding.Leather industry: artificial leather processing.Textile printing and dyeing: heat setting, drying, baking, evaporation, melting.Chemical fiber: polymerization, melt spinning, weaving machine processing, molding, thermosetting, stretching, drying.Paint: paint baking, drying, high temperature solid melting, home appliances, vehicle baking paint, painting.Automotive aircraft: painted baking, drying, thermoforming, high temperature bonding.Wood processing: hot pressing, drying, wood processing and wood products (materials, furniture), wood-based panels
  • What is the reason for pump in the gas-fired boiler does not transfer oil? 2018-07-12
    Question details (performance):A pump in a gas boiler does not transfer oil. Answer: Fault reason:(1) Pump failure.(2) Oil pressure and power are reduced.(3) The oil inlet valve is not sealed.(4) The inlet pipe is not sealed.(5) The interceptor valve is closed.(6) The filter is contaminated.(7) The filter is not sealed.(8) The tubing is not sealed.(9) Pump suck air inlet.(10) The vacuum degree in oil tube is too high.Troubleshooting:(1) Replace with new pump.(2) Remove the inlet valve and clean or replace it.(3) Seal the inlet pipe.(4) Open.(5) Cleaning.(6) Replace the sealing ring.(7) Tighten and exhaust.(8) Clean the filter and valve.
1 2 3 4 5