Question details (performance):Fail ignite, normal pressure, has electricity.Answer: Fault reason:1. The ignition transformer is burnt out.2. The high-voltage wire is damaged or detached.3. The clearance is too large or too small, and the relative size of the ignition rod position is wrong.4. Electrode rupture or grounded short circuit.5. Improper spacing. Troubleshooting:1. Replace with a new one.2. Reinstall or replace.3. Readjustment.
(Question details) specific performance:The gas boiler is powered on, press start, the motor does not turn. Answer: Fault reason:1. Insufficient pneumatic locking.2. The solenoid valve is not sealing, and there is air leakage at the joint. Check the lock.3. The thermal relay is open.4. At least one of the conditional circuits is not valid (water level, pressure, temperature and to check whether the program controller is energized to start). Troubleshooting:1. Adjust the air pressure to the requested value.2. Clean or repair solenoid valve pipe joint.3. Check whether the component is damaged and motor current by reset.4. Check whether the water level, pressure and temperature exceed the limit.ZOZEN gas-fired boiler adopts automatic control to control the operation, combustion, water level, temperature and steam pressure. In case of such problems, the system will automatically prompt the error code.
Using artificially softened water in the heating circuit with your boiler can potentially cause issues and is not recommended.
Artificially softened water contains high levels of sodium ions, which can cause corrosion of the boiler and other components in the heating system. This corrosion can damage the boiler and other components, leading to leaks and reduced efficiency.
In addition, artificially softened water can cause problems with water pressure and flow rate, which can i...
The boiler water film dust remover uses dust-containing gas to impact the inner wall of the dust remover or other special components, and forms a water film in some way, so that the dust in the flue gas is captured by the water film, thus purifying the gas.
Deaerator is one of the key equipment in boiler and heating system. With the popularization and development of demineralized water treatment technology, deoxidization of boilers and heating systems becomes more and more important.
In the industrial boiler industry, it is generally divided into four grades: A, B, C and D according to the production qualification license grade, among which, when purchasing boilers, users often consider Grade A boiler manufacturers. What is a grade A boiler?
Power boilers take the chemical energy stored in fuel, convert it to heat energy in the combustion process, and transfer that heat energy to water to produce steam. The transfer of energy from combustion gases to the water and steam is called heat transfer.
Steam and hot water play an integral role at several stages of the textile manufacturing process. Much of the manufacturing process requires the use of steam or hot water produced by industrial boilers, textile engineering, bulk fabric production, garment manufacturing, or other textile processes.
Pre-treatment
There are several steps in this process, and some of them require both steam and hot water that is clean and pure, which requires an efficient steam boiler.
Dyeing
Dep...