On a steam raising boiler there are three clear applications for level monitoring devices:
1) Level control - To ensure that the right amount of water is added to the boiler at the right time.
1) The entire plant may be purchased as a complete package, only needing securing to basic foundations, and connecting to water, electricity, fuel and steam systems before commissioning. This means that installation costs are minimised.
2) This package arrangement also means that it is simple to relocate a packaged shell boiler.
3) A shell boiler contains a substantial amount of water at saturation temperature, and hence has a substantial amount of stored energy which can be called upon to cope with short term, rapidly applied loads.
*This can also be a disadvantage in that when the energy in the stored water is used, it may take some time before the reserve is built up again.
4)The construction of a shell boiler is generally straight forward, which means that maintenance is simple.
5)Shell boilers often have one furnace tube and burner. This means that control systems are fairly simple.
Although shell boilers may be designed and built to operate up to 27 bar, the majority operat
If the boiler gives overpressure indicator which affects boiler's safe operation, depressurization measures should be taken. However, please pay attention that depressurization can not be too fast. After the overpressure problem of steam boiler is solved, we should check the internal and external parts of boiler to ensure that everything is going well.
1. During the start-up process of the burner, if the burner repeatedly alarms and locks, it should be found out the reason, find the fault and eliminate it, and then press the reset button to inherit the start. Note: The continuous press of the reset button should not exceed 10 seconds
2. If the burner is not successful in one combustion, the natural gas boiler induced draft fan should be restarted, and the second combustion can be started after 5 minutes of ventilation.
3. In the normal operation era, the burner close to the thermal equipment department (such as the connecting flange, etc.) will be very hot, to prevent the formation of burns. Do not place flammable materials in the vicinity to avoid causing fire.
4. During the operation of natural gas-fired boilers, it is necessary to closely supervise the working conditions of hot water circulation pumps and natural gas-fired boiler pressures, natural gas distribution bags, pipeline valves, pressure gauges, flow meters, and water
(Question details) Specific performance:The temperature difference between the inlet oil and the outlet oil temperature of the boiler exceeds the given value.Answer:Cause of failure:(1) The oil supply of the heat oil circulating pump is insufficient.(2) The boiler operates overload.(3) Thermal oil metamorphism.(4) The boiler does not match the heating equipment.(5) Bad insulation effect.(6) There is gas or steam in the thermal oil. Troubleshooting:(1) Remove the faults of oil pump and pipeline.(2) Operate at normal load.(3) Change new oil.(4) Choose proper boiler.(5) Check the insulation layer and repair the loopholes.(6) Remove air or steam. ZOZEN pays much attention to boiler furnace insulation also, the inside is made of high quality insulation material, external use of stainless steel plate, which can maximumly reduce heat loss and improve the operating environment.
Question details (performance):Black smoke happens during operating. Answer: Fault reason:(1) Insufficient air volume, improper air distribution, low furnace temperature: boiler usually equipped with air preheater, but when the air preheater has leakage, hot air flow doesn't satisfy the need of burning, smoke will happen.(2) In the case of stalling situation in full automatic oil-fired boiler: significant increase of furnace negative pressure, no flame can be seen from the inspection hole, steam pressure and steam temperature drop, the steam flow decreases sharply. The water level drops suddenly and then rises sharply.(3) Incomplete fuel burning: this is the main cause of boiler smoke, in the operation, some combustible gases such as carbon monoxide, hydrogen, methane will be generated in addition to carbon dioxide, sulphur dioxide, water vapor and oxygen, nitrogen, etc. during incomplete combustion. They burn and generate black smoke. Incomplete combustion of fuel will not only lead t