For the selection of heat fluid boilers, first step is to determine several parameters: thermal power in the process, the oil temperature, and the use of waste heat.There are several methods for determining the boiler's thermal power:1. Calculation. According to the specific heat capacity of the material to be heated, the heating temperature difference, the processing amount per unit time, etc., the thermal power is equal to the product of the above three points, and the calculation result considers a certain margin amount as the boiler capacity.2. The sum of thermal power in the process equipment can also be used as the basis for the heat power.3. Refer to the experience of the same industry to increase or decrease on the basis of peers.4. If steam heating is used, it can be converted into heat transfer oil of the same tonnage and the capacity is appropriately reduced.The determination of the temperature of the heat transfer oil can be determined according to the characteristics of th
Question details (performance):A pump in a gas boiler does not transfer oil. Answer: Fault reason:(1) Pump failure.(2) Oil pressure and power are reduced.(3) The oil inlet valve is not sealed.(4) The inlet pipe is not sealed.(5) The interceptor valve is closed.(6) The filter is contaminated.(7) The filter is not sealed.(8) The tubing is not sealed.(9) Pump suck air inlet.(10) The vacuum degree in oil tube is too high.Troubleshooting:(1) Replace with new pump.(2) Remove the inlet valve and clean or replace it.(3) Seal the inlet pipe.(4) Open.(5) Cleaning.(6) Replace the sealing ring.(7) Tighten and exhaust.(8) Clean the filter and valve.