  • What are the causes of water attack in the economizer and condenser of a gas-fired boiler? 2018-11-23
    The air in the economizer and condenser has not drained yet when firing. The safety valves of economizer and condenser need to be turned on to exhaust steam. Return pipe valves also need to be turned on, enabling the steam in the economizer and condenser to return to softened water tank. The outlet water temperature is so high that economizer and condenser will have vaporization phenomenon. The outlet water temperature of economizer and condenser need to be controlled. The check valve of the...
  • What is difference between thermal oil heaters and steam boilers? 2018-08-30
    1. They are all a heat conversion device. The heat transfer medium they use is different. The water used in the steam boiler is heated to become steam. The heat transfer medium of thermal oil heater is heat medium oil. The heat is transferred to the heated substance by the heat medium oil.2. When a higher heating temperature is required, such as 280 degrees, the steam pressure of the steam boiler should reach 7MPa or more, and the process piping and heat exchange equipment must also withstand the same pressure. The equipment cost is high and dangerous. Thermal oil heater provides a temperature above 280 degrees, but the pressure is lower than 1MPa.3. The temperature of thermal oil heater can be accurately controlled within 3 degrees and the temperature of the steam changes greatly.4. Thermal oil heater is used alone, the exhaust gas temperature is higher, and the thermal efficiency is lower than that of the steam boiler. However, if used in conjunction with a steam boiler, the
  • Why does the biomass-fired boiler smoke in operation? 2018-07-12
    Question details (performance):Black smoke happens during operating. Answer: Fault reason:(1) Insufficient air volume, improper air distribution, low furnace temperature: boiler usually equipped with air preheater, but when the air preheater has leakage, hot air flow doesn't satisfy the need of burning, smoke will happen.(2) In the case of stalling situation in full automatic oil-fired boiler: significant increase of furnace negative pressure, no flame can be seen from the inspection hole, steam pressure and steam temperature drop, the steam flow decreases sharply. The water level drops suddenly and then rises sharply.(3) Incomplete fuel burning: this is the main cause of boiler smoke, in the operation, some combustible gases such as carbon monoxide, hydrogen, methane will be generated in addition to carbon dioxide, sulphur dioxide, water vapor and oxygen, nitrogen, etc. during incomplete combustion. They burn and generate black smoke. Incomplete combustion of fuel will not only lead t
  • Why the slag discharge tube of circulating fluidized bed boiler will be blocked? 2018-07-12
    (Details on the problem) Specific Performance:Slagging pipe blocks during operation of circulating fluidized bed boiler. Answer:cause of failure:(1) The internal shape is caused by the limited expansion of the wear-resistant material inside the slag discharge pipe. The internal components of the slag cooler are deformed, affecting the fluidization of the slag cooler; the slag cooler is deactivated for a long time or a single slag cooler is selected for slagging, and the bed material in the deactivated slag cooler is bonded under the influence of steam, which being low temperature coke.(2) The operating personnel did not grasp the ratio of the fluidized air volume of the slag cooler. Inappropriate air volume ratio resulted in poor ash slag fluidization in the slag cooler. Troubleshooting:(1) Operation personnel should strengthen understanding of boiler operating conditions, adjust boiler parameters in a timely manner, set up the concept of boiler material dynamic balance, control boiler