(Question details) specific performance:The gas boiler is powered on, press start, the motor does not turn. Answer: Fault reason:1. Insufficient pneumatic locking.2. The solenoid valve is not sealing, and there is air leakage at the joint. Check the lock.3. The thermal relay is open.4. At least one of the conditional circuits is not valid (water level, pressure, temperature and to check whether the program controller is energized to start). Troubleshooting:1. Adjust the air pressure to the requested value.2. Clean or repair solenoid valve pipe joint.3. Check whether the component is damaged and motor current by reset.4. Check whether the water level, pressure and temperature exceed the limit.ZOZEN gas-fired boiler adopts automatic control to control the operation, combustion, water level, temperature and steam pressure. In case of such problems, the system will automatically prompt the error code.
There are several ways to estimate the thermal efficiency of gas-fired boilers:
1. Direct method: This method involves measuring the amount of fuel consumed and the amount of heat produced by the boiler. By comparing these two values, it is possible to calculate the thermal efficiency of the boiler.
2. Indirect method: The indirect method involves measuring various parameters such as flue gas temperature, ambient air temperature, and fuel consumption, and then calculating the t...
Using artificially softened water in the heating circuit with your boiler can potentially cause issues and is not recommended.
Artificially softened water contains high levels of sodium ions, which can cause corrosion of the boiler and other components in the heating system. This corrosion can damage the boiler and other components, leading to leaks and reduced efficiency.
In addition, artificially softened water can cause problems with water pressure and flow rate, which can i...
Load tracking is an important feature of industrial boilers that helps to optimize their performance and efficiency. Load tracking refers to the ability of a boiler to adjust its output in response to changes in demand.
In an industrial setting, the demand for steam or hot water can vary significantly depending on factors such as production schedules, weather conditions, and other variables. Load tracking allows the boiler to adjust its output to match the changing demand, ensuring that...
The higher heating value of natural gas refers to the total heat released when a specified amount of natural gas is completely burned, including the latent heat of vaporization released by the condensation of water vapor in flue gas into water.
The lower heating value of natural gas refers to the heat released when a specified amount of gas is completely burned, the temperature of combustion products is the same as the initial temperature of natural gas, and the generated steam remains ...
Drum boiler refers to boiler equipment with boiler drum, which is an important pressure component in natural circulation boiler and the connecting hub of the three processes of boiler heating, vaporization and overheating, and plays a connecting role. Water becomes qualified superheated steam in the boiler, which goes through three processes: heating, vaporization and overheating. Heating from feed water to saturated water is a heating process; The vaporization of saturated water into saturated steam is a vaporization process; Heating saturated steam into superheated steam is an overheating process.
At the same water temperature, the larger the excess amount of oxygen scavenger in water, the faster and more complete the chemical reaction. Under the same dosage, the higher the water temperature, the better the deoxidization effect. Under the same deoxidization effect, the higher the water temperature, the smaller the dosage.
First of all, don't panic. According to the normal shutdown sequence, check whether the fuel, steam and water valves of gas-fired boiler meet the shutdown requirements.
Secondly, close the surface blowdown valve of the gas-fired boiler to prevent other faults of the boiler. Then, quickly close the main steam valve to prevent the gas boiler drum from losing water.
Thirdly, close the deaerator air supply valve, the main power switch and the natural gas valve. The air inlet of the gas-fired boiler burner should not be blocked to reduce the area of the air inlet, and the room ventilation should not be blocked to avoid the formation of toxic and harmful gases.