It could also say, how much heat is required to rais the water temperature from 60 ℃ to 90 ℃.
To calculate heat required follow below steps
Q= mCp dt
Where
m - water flow rate (kg/hr)
Cp- specific heat of water
dt- temperature differences ( 90–60)
You will get heat required in kcal/ hr.
dividing to Q by fuel GCV and system efficiency you will come to know how much fuel (either it is coal or oil) required to raise the temperature of water from 60 ℃ to 90℃.
1.Primary air is used for transportation of fine coal particle from coal mill to boiler floor at different elevations as per requirement.
2.Primary air is used for preheating of moisturised coal in to the coal mill so that minimum energy is required for combustion of the same.
3.As we all know that only 23% oxygen is available in the air by weight. For combustion of huge quantity of coal inside the boiler very high quantity of oxygen is required. This oxygen requirement will be completed by secondary air which is supplied by FORCED DRAFT fans through ducts.
This secondary air is coming via air preheater hence its outlet temperature increases this will help in combustion and low heat input is required for combustion of coal.
Boiler efficiency is mainly depended on the amount of losses in the system. In high capacity pulverized coal fired boilers the total losses account to about 12 to 14%. Roughly 50% of the losses are governed by fuel properties like hydrogen in fuel, moisture in fuel and ambient air conditions. The other 50% losses are carbon loss and dry gas loss. The best efficiency in the boiler can be achieved if the losses are kept to the minimum. Since 50% of the losses are dependent on the fuel and ambient condition, the best efficiency can be achieved by properly tuning the other 50%, i.e. mainly carbon loss and dry gas loss.
The coal-fired steam boiler is a forced circulation high-pressure single-tube DC boiler. Its operation process includes three processes: the combustion process of the fuel, the heat transfer process of flue gas to water and the vaporization process after water absorbs heat. In order to better control these different processes, the control system should make
the heat of pulverized coal combustion adapt to the requirements of steam load changes and dryness.
If you smell gas, don’t use electrical switches, telephones, or any appliances that may cause sparks.Firstly, you should shut off the gas valve, open the doors and windows to circulate the air. Then you should seek for professional help:
The following conditions will occur when a gas-fired boiler is leaking:
The working pressure of natural gas changes.
There is a strong airflow sound near the source of the leak.
The hand-held alarm makes an abnormal sound.
If the boiler has a serious leakage, the fixed alarm will issue an automatic alarm and the exhaust fan will be opened automatically.
1.Flamelifting caused by a sudden increase of gas pressure;
2.Gas supply disruptions caused by malfunction of solenoid valve;
3.Great gas constituent change and excessive moisture content.
1. The control system is equipped with a special computer controller, which makes the boiler running clear and easy to operate.
2. The burner is controlled by full-automatic program, and in case of failure, the burner stops automatically.
3. The boiler body is designed with reasonable structure, and the top is equipped with air vent. The boiler works under normal pressure and is far away from explosion danger. The full wet back three-way structure and corrugated tank design are adopted. The flue gas process is long, the temperature of exhaust gas is reduced, the heat transfer coefficient is increased, and the equipment life is prevented from being reduced due to the expansion and contraction of metal.