Make-up water rate refers to the proportion of treated water added to the boilers, steam turbine equipment and its thermal systems and participating in the circulation of steam-water systems in the boiler steam volume in the calculation period.
Prepare relevant technical data, including technical data of boiler manufacture and installation, boiler use registration data, boiler operation records, water quality test records, repair and modification records, accident records and previous inspection reports;
The environmental thermal oil heater refers to a boiler heated by heat transfer oil. Heat transfer oil, also known as organic heat carrier, has been used as an intermediate heat transfer medium in industrial heat exchange for more than 50 years.
Ensure that the vent valve on the boiler is open and check there is no pressure in the boiler. Check that the steam stop valve is closed. Check that all the valves for fuel are open, and let the fuel circulate through the system until it comes to the temperature required by the manufacturer recommendation.
A hot water boiler should be thoroughly inspected at first, including the accessory pipeline. Close the drain valve and open the gauge cock to discharge the air in the boiler.
The installation contents of boiler body pipeline are as follows:
1) Connection between water supply console and economizer header;
2) Connection between economizer and inlet pipe from economizer outlet to drum;
3) Connection between the main pipe and branch pipe of the drum drop and each lower header of the water wall;
4) Connection of steam guide pipe between each water wall header and steam drum;
5) Connection of superheated steam pipe between outlet header of low-temperature superheater...
All boiler pipes have been installed and passed the hydrostatic test.
The furnace wall masonry and insulation work have all ended and has been qualified.
The flue gas duct has been installed and insulated, and the induced draft fan has been installed and debugged to be qualified and can be put into operation.
All the thermal and electrical instruments required for boiler drying have been installed and verified to be qualified.
Mortar samples have been placed on both sides of the middle par...
Chain grate has certain selectivity for coal types, and soft coal with volatile content above 15%, ash melting point above 1250℃, moderate particle size and calorific value above 18800~21000kJ/kg is more suitable.