zozen boiler
HomeBoiler tagscoal fire 10 tph Boiler

“coal fire 10 tph Boiler”- related faq

  • In the case of a thermal oil heater that is in a high-temperature operation state, how should it be handled correctly in the event of a sudden power failure? 2019-12-06
    In the case of a thermal oil heater in a high-temperature operation state, if it encounters an emergency situation of power failure, its correct treatment is: When the circulating oil pump cannot operate normally due to power failure, the heat transfer oil in the furnace tube will exceed the allowable value in a short time due to the residual heat of the furnace. At this time, the cold oil switching valve should be opened to release the cold oil in the expansion tank. And sent to the oil storage tank. At the same time, wet coal pressure or emergency shutdown is required and needs to be completed within 5 minutes. In addition, we need to pay attention to not to put the oil in the expansion tank clean, otherwise the system will inhale air and cause problems. An oil level mark can be made on the oil level of the oil storage tank. When the cold oil is replaced, the valve can be closed in time to avoid the expansion of the expansion tank and the oil storage tank.
  • What are the most common boiler fuel types? 2019-08-23
    Boilers are often distinguished by fuels that power them. The kind of fuel makes an essential difference in operating costs and environmental impact, so it’s important to learn about the various types of boiler fuel. Coal, is a common boiler fuel. It dominates the global energy arena due to its abundance, affordability and wide distribution across the world. The most commonly used coal fuels include anthracite, bituminous coal, sub-bituminous coal, lignite and peat.
  • Breakdown of Coal Feeding System during Operation of Circulating Fluidized Bed. 2018-07-12
    (Question Details) Specific Performance:Broken coal is one of the most common failures of the coal feeder. The coal feeder is the lifeline of the boiler. Its normal operation is the basic guarantee for the normal and stable operation of the boiler, because it’s common occurrence that the coal feeder breaks the coal, especially when multiple coal feeders broken coal simultaneously, the improper handling resulting in overheating, explosion, coking, shutdown and other failures. Answer:cause of failure:(1) The particles of fluidized bed boiler fuel are coarse, but the fine particles in the fuel have a large amount of moisture. It is very easy to bond, resulting in the clogging of coal bunker and coal feeder.(2) Coal particles are jammed and squeezed in the coal feeder, causing the coal feeder chain to break.(3) Impurities in coal, such as woven bags and tree blocks, enter the coal feeder, causing coal feeders to jam, blockage, trip and break pins. Troubleshooting:(1) Fluidized Be
  • Why are there percussive sounds and vibrations in the boiler drum or pipe of a coal-fired boiler? (water impact) 2018-07-12
    Question details (Performance):The steam pipe vibrates violently and has a dull impact sound.Answer:  fault reason: There is air in pipeline  ; automatic air vent valve is not turned on; or it is out of order. Troubleshooting: Check all the air release valves on the water supply pipe and the air release valves on the top of the boiler tube for gas storage. If the valve fails, it should be replaced immediately.
  • What is the reason for the failure of the coal economizer pipe of the coal-fired boiler? 2018-07-12
    Question details (Performance):1. The furnace wall at the coal economizer leaks water and steam with abnormal sound.2. The water level in the boiler drops sharply, and the water supply is obviously greater than the evaporation capacity.3. Smoke exhaust temperature and water outlet temperature rise.Answer: Fault reason:1. The water quality does not reach standard, and the oxygen in the water is decomposed into corroded pipe walls when the temperature rises.2. The low feed water temperature and smoke exhaust temperature make the inner and outer wall of the coal economizer pipe produce acid corrosion, or flying ash wear the pipe wall thin. 3. The pipe is blocked by impurities, causing overheating.4. Poor materials, defects in manufacturing, installation and maintenance. Troubleshooting:1. When economizer is slightly broke, it still maintains boiler operation, and the gap seems will not expand rapidly, in this case, load operation should be reduced, and start the spare boiler immediately,
  • Why are the furnace tubes damaged in operation of coal-fired boilers? 2018-07-12
    (Question details) Specific performance:The wall thickness of several boiler tubes was significantly reduced in a large area, the remaining wall thickness was 2.0mm, and some furnace tubes were corroded and worn out. Furnace tube wall is covered with a thick layer of uneven scale, the surface of the scale is brick red and black, scale layer is loose, and it is easy to remove the inner wall of the furnace tube, after removing, the furnace tube wall covered with a layer of corrosion pits. There is a thin layer of brick red corrosion on the outer wall of boiler tube, some of which are attached with black adhesive. Answer: Fault reason:1. The boiler is seriously short of water.2. Poor water circulation and uneven combustion.3. The unqualified quality of the boiler water and undemanding chemical supervision make the inner wall of the pipe corrode and scale, causing the pipe overheat and reduction of the strength.4. Due to the presence of impurities and scale, the furnace tube is blocked ins
12 3 4 5 6 7 8 9