  • How to deal with emergency low boiler water level? 2020-06-05
    Normally a boiler is provided with two independent sensors for emergency low water level burner cut-outs. So this would never happen. However, if it does, don't take any chances! Shut off the burners immediately!  Before you start raising the level in the boiler you have to find out if any part of the furnace walls has been overheated. If you raise the level over a glowing steel-wall then the boiler might produce more steam than the safety valves can handle and a nasty explosion would be the result.
  • Why the boiler load can not be increased to peak conditions? 2020-06-05
    Soot on the heating surfaces. Even a thin layer of soot will reduce the boiler efficiency. Not the right fuel for the burner. For instance, diesel oil to a rotary cup burner wouldn't do. Too low feed water temperature.
  • What are the characteristics of dust collector of coal-fired boiler? 2020-05-29
    The characteristics of dust collector of coal-fired boiler: 1) Separating the particulate matters. The dust collector of coal-fired boiler can effectively separate the big particulate matters with ignition conditions, so as to reduce the obstruction of dust removal system and improve efficiency. 2) Reducing dust. The dust collector of coal-fired boiler can prevent the dust-contained gas from washing the bag to lower the dust concentration of dust-contained gas and extend the service life of filtering bag and pulse magnetic valve. 3) Adopting materials with high quality. The dust collector of coal-fired boiler adopts high-temperature resistant materials that can extend the service life of dust collector. 4) Adopting elastic piston ring. The mouth of filtering bag adopts elastic piston ring to ensure the leakproofness, which is firm and reliable.
  • What is the proper way to clean a steam boiler? 2020-05-29
    There are many opinions on the best way to clean a steam boiler. One of the oldest ways is to dissolve a pound of tri-sodium phosphate (TSP) and a pound of caustic soda (lye) in water and pour it into the boiler. Let it cook for a few hours and then drain the boiler. If you can't buy TSP in your town, try a commercial soap called MEX. It works well and will not damage the rubber gaskets found in some boilers. However, before you clean any boiler, check the manufacturer's instructions for their recommendations. 
  • What are the causes of coal erosion in boiler 2020-05-22
    The causes of coal erosion as distinct from all the other types of erosion are many but from a theoretical point of view are simply high velocity particles impacting and rubbing along the surface of the tubes. The boiler designer minimises this by providing a volume in the furnace and a direction of travel of the coal such that it is burned before it can touch the tubes. This can be defeated by increasing the velocity reducing the combustibility or increasing the mass flow. All of these parameters occur if you reduce the calorific value of the fuel or overload the boiler. If you had no erosion before changing your fuel that is the cause. If you have never had design fuel you dont know if it would have eroded anyway. If it would the cause will be a different reason such as arodynamic flows and aiming of the burner or size of the tartget fireball centre. This is a serious problem and should be dealt with by an experienced expert.
  • How much coal is required to boil water from 60℃ to 90℃ in boiler 2020-05-22
    It could also say, how much heat is required to rais the water temperature from 60 ℃ to 90 ℃. To calculate heat required follow below steps Q= mCp dt Where m - water flow rate (kg/hr) Cp- specific heat of water dt- temperature differences ( 90–60) You will get heat required in kcal/ hr. dividing to Q by fuel GCV and system efficiency you will come to know how much fuel (either it is coal or oil) required to raise the temperature of water from 60 ℃ to 90℃.
  • What are the functions of primary air and secondary air in a pulverized coal fired boiler? 2020-05-22
    1.Primary air is used for transportation of fine coal particle from coal mill to boiler floor at different elevations as per requirement. 2.Primary air is used for preheating of moisturised coal in to the coal mill so that minimum energy is required for combustion of the same. 3.As we all know that only 23% oxygen is available in the air by weight. For combustion of huge quantity of coal inside the boiler very high quantity of oxygen is required. This oxygen requirement will be completed by secondary air which is supplied by FORCED DRAFT fans through ducts. This secondary air is coming via air preheater hence its outlet temperature increases this will help in combustion and low heat input is required for combustion of coal.
  • What parameters are critical to the health of a coal-fired boiler? 2020-05-15
    Few parameters critical to health of the Boiler are (4)Heat rate of the Boiler. This is a composite index of many performance indicators. Most of them will appear below. (5)Unburnt fuel in flue gas and at boiler bottom . (6)Flue gas furnace exit temperature. (7)Boiler tube metal temperatures. (8)Oxygen in flue gas. (9)Imbalances in flue gas temperature over a cross section. (10)Spray water consumption in Super heater and Reheater. (11)Heat radiation from insulation. The above all affects the performance of the boiler.