  • What maintenance does a biomass boiler require? 2019-05-10
    We would recommend your biomass boiler has at least an annual maintenance service. Like anything if you maintain your boiler correctly it will last longer and perform better. Biomass boilers burning even the most difficult of materials can operate unattended, but weekly inspection visits are required to carry out a visual inspection of the boiler and fuel feed system, to check the lubrication of bearings and to empty the ashbin. As a large enterprise specializing in manufacturing boilers, ZOZEN...
  • What conditions are required for the full combustion of biomass-fired boiler fuel on the chain grate? 2019-03-21
    1. Rational air distribution, supply sufficient and rational air by region; 2. Appropriate furnace temperature;3. Suitable air turbulence and mixing in furnace;4. Fuels remain long enough on chain grate and in the furnace;5. Keep a reasonable distance between the fuel hopper and the flame fronts to avoid igniting fuels in the hopper.The biomass-fired boilers are optimally designed according to the characteristics of different biomass fuels. ZOZEN will customize the biomass-fired boiler for ...
  • What are the phenomena of coking on the circulating fluidized bed boilers? 2018-11-23
    The bed temperature rises sharply. Oxygen levels go down and sometimes drop to zero. The electric current of primary air fan is less and wind pressure of air compartment is higher. Negative pressure of furnace is increased while the electric current of induced draft fan is reduced. The slag discharge is difficult or unsuccessful. When appearing bed clinkering, the bed temperature and bed pressure will be uneven distributed and not at normal condition; the measuring point of part bed tempe...
  • There is hammer sound, vibration and unstable pressure during the operation of thermal oil heater. 2018-07-12
    (Question details) Specific performance:There is hammer sound in the oil inlet pipe, and the pointer of the inlet and outlet pressure gauge fluctuates.Answers: Cause of failure:The system contains gas and moisture.Troubleshooting:(1) Exhaust air.(2) Cook oil.
  • What about the high failure rate of fuel delivery system of biomass-fired boiler? 2018-07-12
    Question details (Performance):There is no feeding machine between hopper and # 0A/B belt, which causes unstable feeding and feeding amount cannot be controlled, during running, big amount material presses on belts which affect normal operation of the belt.Answer: The cause of the problem: Because the toughness of the biomass fuel is bigger, the proportion is small, material level should not be too high, otherwise it will occur block, so conveying system is normally running 24 hours, moving parts are easy to wear and cause high failure rate; also the length of the cut grass is difficult to guarantee its length between 8 ~ 15cm, and it is easy to get stuck in the feed machine before the furnace and it is difficult to clean, which has a great impact on the load of the boiler. Troubleshooting: 1. To reduce wearing and expand the service life of equipment, general motor adopts variable frequency motor, slow down the running speed, to control the rate of fuel feeding, make material's stacki
  • How to solve the problem of coking in circulating fluidized bed boiler operation? 2018-07-12
    (Question Details) Specific Performance:(1) The bed temperature has risen sharply.(2) The oxygen level drops even to zero.(3) The current of the primary blower is reduced, and the wind pressure in the wind chamber is high and fluctuates.(4) The furnace negative pressure increases and the induced draft fan current decreases.(5) Difficulties in slagging.(6) If coking in low temperature, the bed temperature, bed pressure distribution is uneven, the deviation is too large, the bed pressure, the plenum pressure, the bed temperature is not normal, and the local bed temperature measurement point is not normally raised or lowered.(7) The bed pressure indicator value fluctuates little. Answer: causes of failure :(1) Improper operation, resulting in overheated bed temperature and coking.(2) The primary air volume during operation is kept too small, which is lower than the minimum fluidized air volume, so that the material can’t be well fluidized but piled up, the temperature field of the entire
  • Why the slag discharge tube of circulating fluidized bed boiler will be blocked? 2018-07-12
    (Details on the problem) Specific Performance:Slagging pipe blocks during operation of circulating fluidized bed boiler. Answer:cause of failure:(1) The internal shape is caused by the limited expansion of the wear-resistant material inside the slag discharge pipe. The internal components of the slag cooler are deformed, affecting the fluidization of the slag cooler; the slag cooler is deactivated for a long time or a single slag cooler is selected for slagging, and the bed material in the deactivated slag cooler is bonded under the influence of steam, which being low temperature coke.(2) The operating personnel did not grasp the ratio of the fluidized air volume of the slag cooler. Inappropriate air volume ratio resulted in poor ash slag fluidization in the slag cooler. Troubleshooting:(1) Operation personnel should strengthen understanding of boiler operating conditions, adjust boiler parameters in a timely manner, set up the concept of boiler material dynamic balance, control boiler