Once the flameout of gas-fired or oil-fired boiler is confirmed, the boiler should be shut down for inspection and maintenance in time according to the operating regulations. Only after the inspection and test are completed, the boiler can continue to be used.
Boiler produces heat via fuel combustion, so the burner is one of the important parts of boiler. And the air supply system is also an important component of burner. Whether the burner works well largely depends on its air supply system.
If the final temperature of feed water doesn’t reach the saturated temperature after being heated by an economizer, (that is, the feed water has not reached the boiling state), we call the economizer as a nonsteaming economizer. Generally, the final temperature is 30-50℃ lower than the saturated temperature.
1. The storage tank is used to store the heat medium oil of the heating system;
2. The storage tank is used to receive the overrunning heat medium oil;
3. The storage tank is used to supplement heat medium oil for the heating system;
4. The storage tank should be placed at the lowest position of the system;
5. A firewall should be placed between the storage tank and the thermal oil heater;
6. The storage tank should be operated at a low liquid level.
The selection of a burner of the gas-fired thermal oil heater should be determined according to the boiler proper structure and fuel characteristics and in combination with the actual conditions and requirements. In addition, this kind of boiler can adopt a waste heat recovery device to improve thermal efficiency and reduce heat energy loss.
The gas consumption of 10 tph gas-fired boiler is related to technical parameters.
Such as heating surface layout, heat preservation effect, heat loss, water capacity, etc. The calculation formula of gas consumption of 10 tph gas-fired boiler is as follows:
=10 tph gas-fired boiler output÷ thermal efficiency ÷calorific value of natural gas
= 6,000,000 kcal ÷ 0.98 ÷ 8,600 kcal / h = 712 m3
Therefore, the gas consumption of 10 tph gas-fired boiler is 712 m3/ h
The gas consumption of the above gas-fired boiler is calculated at full capacity. In practice, the gas consumption changes with the operation load and operation conditions. In addition, if thermal efficiency of the gas-fired boiler is different, the gas consumption is different, too. The higher thermal efficiency is, the lower gas consumption is.
Excess air provides safe operation above stoichiometric conditions. A burner is typically set up with 15% to 20% excess air in higher firing ranges. Higher excess air levels result in fuel being used to heat the air instead of transferring it to usable energy, increasing stack losses and significantly decreasing efficiency. Boilers with lower excess air throughout the operating range have higher efficiencies.