(1) The boiler and all auxiliary equipment are installed, and all tests such as ball passing test, hydrostatic test and air tightness test are qualified.
(2) All rotating devices, feed water pumps, condensate pumps, salt solution pumps, blowers and induced draft fans for coal conveying, combustion and ash removal are qualified for trial operation.
(3) The fuel and water supply are guaranteed, the steam, water and flue gas piping system are normal, and the connection unrelated to the boiler to ...
Before the boiler is put into operation, the furnace wall and arch must be baked and dried, which is called furnace drying. Furnace drying is to slowly dry the damp furnace wall and arch with warm fire to prevent ignition without furnace drying, causing cracking, deformation and serious damage.
The higher heating value of natural gas refers to the total heat released when a specified amount of natural gas is completely burned, including the latent heat of vaporization released by the condensation of water vapor in flue gas into water.
The lower heating value of natural gas refers to the heat released when a specified amount of gas is completely burned, the temperature of combustion products is the same as the initial temperature of natural gas, and the generated steam remains ...
As a kind of special equipment, industrial boiler is special and complex. Complete inspection can ensure the safety operation of the boiler.
The external inspection of the boiler is generally conducted once a year, the internal inspection is generally conducted once every two years, and the hydrostatic test is generally conducted once every six years.
For boilers that cannot be inspected internally, a water pressure test should be conducted every three years. The internal ...
ATMOSPHERIC BOILER - a boiler in which combustion air/flue gases are drawn through the boiler without a fan. Modulating atmospheric boilers are designed to control the output (size of flame) to match the boilers variable load requirements. During this process the burner is designed to stay at the correct fuel / air ratios across the complete firing range ensuring maximum combustion and boiler efficiencies. Modulation refers to a boiler's ability to match firing rate - input - to meet the heating demand - output - of the system. (https://tlj-eng.com/news/heating-boilers-what-you-need-to-know.html)
The steam cylinder of the boiler is the main supporting equipment of the boiler, which is used to distribute the steam generated during the operation of the boiler to various pipelines. The steam cylinder of the boiler is a pressure vessel, and its loading capacity and volume should correspond to the supporting boiler.
The boiler water level gauge is a detection instrument that shows the water level of the boiler, and it is one of the important safety accessories of the steam boiler.
Boiler parameters are the main indicators of boiler performance, including boiler capacity, steam pressure, steam temperature, feed water temperature, etc. Boiler capacity can be expressed by rated evaporation or maximum continuous evaporation. Rated evaporation is the amount of steam continuously produced per unit time under the specified outlet pressure, temperature and efficiency. The maximum continuous evaporation is the maximum amount of steam that can be continuously produced per unit time under the specified outlet pressure and temperature.