Steam carries about 540 Kcal/kg of useful energy whereas hot water and thermal fluid carry much less energy. Steam does not require a pump to transfer the energy. Generally, if the heating temperatures required are <100°C, then hot water can be used and if temperatures >180°C are needed then thermal fluid might be a better choice. For process temperatures between 100°C and 180°C steam is considered a viable option.
The air in the economizer and condenser has not drained yet when firing. The safety valves of economizer and condenser need to be turned on to exhaust steam. Return pipe valves also need to be turned on, enabling the steam in the economizer and condenser to return to softened water tank.
The outlet water temperature is so high that economizer and condenser will have vaporization phenomenon. The outlet water temperature of economizer and condenser need to be controlled.
The check valve of the...
(Question Details) Specific Performance:(1) There are blasting sounds in the furnace, and the furnace chamber is under positive pressure. There is smoke emitted from the combustion chamber in a leakage. In severe cases, the explosion-proof door of the boiler body opens.(2) Drum water level drops rapidly and the feedwater flow rate is not abnormally larger than steam flow. MFT acts when the water level is below -280mm.(3) Drum pressure, steam flow rate, exhaust temperature decrease, smoke temperature difference increases on both sides.(4) The negative pressure at the inlet of the flue and suction fan becomes smaller and the temperature difference between the two sides increased. (5) Smoke temperature decreases at the inlet and outlet of the cyclone separator, and the temperature of the material returned is low.(6) Bed pressure increases, bed materials clean, fluidization poof, bed temperature distributes unevenly and bottom slag discharge difficultly. Answer:cause of failure:(1) Fly ash
Question details (Performance):1. The furnace wall at the coal economizer leaks water and steam with abnormal sound.2. The water level in the boiler drops sharply, and the water supply is obviously greater than the evaporation capacity.3. Smoke exhaust temperature and water outlet temperature rise.Answer: Fault reason:1. The water quality does not reach standard, and the oxygen in the water is decomposed into corroded pipe walls when the temperature rises.2. The low feed water temperature and smoke exhaust temperature make the inner and outer wall of the coal economizer pipe produce acid corrosion, or flying ash wear the pipe wall thin. 3. The pipe is blocked by impurities, causing overheating.4. Poor materials, defects in manufacturing, installation and maintenance. Troubleshooting:1. When economizer is slightly broke, it still maintains boiler operation, and the gap seems will not expand rapidly, in this case, load operation should be reduced, and start the spare boiler immediately,