What are the operating conditions of boiler MFT protection?
MFT means the main fuel trip. To put it simply, when the protection signal is activated, the control system automatically cuts off the boiler fuel system and links the corresponding systems and equipment, so that the whole thermal system can be safely shut down, the boiler can be protected, and the fault can be prevented from further expanding.
Under any of the following conditions, the boiler MFT protection action condition can be triggered:
(1) two blowers are stopped.
(2) Two induced draft fans are stopped.
(3) Two air preheaters are stopped.
(4) Two primary fans are stopped.
(5) The furnace pressure is extremely high.
(6) The furnace pressure is extremely low.
(7) The drum water level is extremely high.
(8) The steam drum water level is extremely low.
(9) All three water circulating pumps are stopped.
(10) the total wind m of the boiler is lower than 30%fMCR.
(11) fuel loss.
(12) Fire extinguishing in the whole furnace.
(13) Loss of cooling air for fire detection.
(14) press MFT button by hand.
-
SZS series gas-fired (oil-fired) hot water boilerLive Chat7-116 MW1-1.6 MPa
-
WNS series gas-fired (oil-fired) steam boilerLive Chat1-20 t/h0.7-2 MPa
-
DHL series coal-fired steam boilerLive Chat20-75 t/h1.25-5.4 MPa
-
Email us
-
WhatsApp: +86 18861589035
WeChat: +86 13506150756
Live Chat

-
Industrial heating upgrades can have a direct impact on a factory’s production schedule and operational stability. For manufacturers investing in new facilities or upgrading equipment in Vietnam, boiler selection involves more than fuel costs. Process temperatures, continuous heat supply, emission requirements, and long-term maintenance must all be taken into account. Whether transitioning from coal to natural gas or biomass, manufacturers need a heating solution tailored to their actual p...17 Nov 2026 -
From spinning and weaving to dyeing, printing and heat setting, steam is required throughout multiple stages of textile production. As textile enterprises pay closer attention to energy costs, steam supply stability and emission requirements, boiler selection can no longer be based solely on rated evaporation capacity. Local fuel availability, production load, boiler room conditions and ongoing operation and maintenance also need to be considered. Recent textile projects served by ZOZEN Boiler ...10 Nov 2026 -
IntroductionIn Wuhan, Hubei Province, Hubei Hanjia New Materials Co., Ltd. and Wuhan Yiqingsheng Building Materials Co., Ltd. required thermal energy equipment for autoclave curing and continuous production-line heating, respectively. Based on the production processes, fuel conditions and site requirements of the two companies, ZOZEN Boiler supplied an 8 t/h DZL series biomass steam boiler and a 7.2-million-kcal YWW series biomass thermal oil boiler. The two projects use different heat-transfer ...03 Nov 2026