The fuel of coal-fired boiler will release some harmful substances after combustion that are harmful to human body, but also pollute the environment. Therefore, the desulfurization treatment is required for coal-fired boiler, including desulfurization before combustion, desulfurization during combustion and desulfurization after combustion. The specific operating methods are different.
In general, gas-fired boiler uses natural gas to heat water in order to provide heat source for underfloor heating and heating radiator, while condensing gas-fired uses condensation technology to recycle the thermal energy from the exhaust gas.
Influencing factors of slagging on heating surface of boiler
(1) Ash characteristics of pulverized coal
Generally, the softening temperature ST of ash is used as the main indicator of slag formation. Coal with low ash melting point (ST<1200℃) is easy to slag. In addition, the slagging index also includes: silicon ratio, alkali-acid ratio, slagging index, limit viscosity and so on.
(2)Aerodynamic characteristics in the furnace
Improper air flow organization leads to flame center deviation, and the pulverized coal air flow flame adheres to the wall, causing local slagging of the water-cooled wall;
Improper air flow organization, forming flue gas retention vortex area and forming a reducing atmosphere (with CO), reducing the ash melting point and increasing the possibility of slagging.
Excess air coefficient: When the excess air in the furnace is too small, a reducing atmosphere may be generated, and the tendency of slagging will increase accordingly.
(3)Influence of boiler heat lo
Industrial boilers will produce wastes that needs to be treated during the use process, which is what we mentioned of boiler blowdown. What are the methods for boiler blowdown?
1. Regular blowdown
1) The time interval and quantity of discharge depend on the test results of boiler water. It usually do not exceed 5% of the water supply.
2) When the regular blowdown is being made under high load of the boiler, the blowdown of the water-cooled wall header is generally not required to avoid affecting the normal water circulation of the water-cooled wall and forming a tube explosion incident.
2. Continuous blowdown
The amount of blowdown shall be determined according to the test results of the boiler water, and shall be completed by adjusting the needle-shaped angle of the blowdown tube.
The explosion-proof door of the gas-fired boiler is opened or broken when the combustible gas explosion suddenly increases the pressure, it then releases high-pressure gas to reduce the damage to the gas-fired boiler body and also ensure
The function of the gas-fired boiler explosion-proof door is usually reflected when the gas-fired boiler is ignited or running due to improper operation. For instance, the furnace is not purged before ignition, the furnace is still not purged even the ignition cannot successfully be lit, the nozzle is leaking, the fuel is not completely burned, and extinguished failure to cut off fuel quickly, etc. all of them may cause the furnace and tail flue to explode. Installing explosion-proof door for gas-fired boiler is to release the pressure to avoid the accident from expanding and also to ensure the safety of the industrial steam boiler when a slight explosion occurs in the furnace or flue.
A water level sensor fail on a steam boiler is extremely dangerous. The low water cut of should be tested daily. If the sensor fails the boiler could turn all the water into steam, leaving the boiler dry. Without water in the boiler the flame from the burner would heat up the heating surface to extreme temperatures and would crack and damage the inside of the boiler. But that’s not the dangerous part. If water added to boiler while it is extremely hot. Once water touches the extremely hot heating service, water would immediately start to evaporate into steam. When water evaporates it expands 18x it’s original size. The boiler would explode from the sudden increase in pressure from the inside. Some in some cases, boilers that have exploded out of a building and have landed 100s of feet away.