zozen boiler
HomeBoiler tagsboiler flue gas

“boiler flue gas”- related faq

  • What causes the burner motor of the gas-fired boiler not running? 2023-11-24
    If the burner motor of a gas-fired boiler is not running, several issues could be at play. Diagnosing the problem involves checking various components and systems. Here are some common causes: Electrical Issues: Check if there's an electrical supply to the motor. A tripped circuit breaker, blown fuse, or loose wiring could interrupt power supply to the motor. Faulty Motor: The motor itself could be malfunctioning. Over time, motors can wear out or burn out due to electrical issues or mechanica...
  • Why doesn't the gas boiler's motor turn on after pressing the start button? 2023-11-24
    (Question details) specific performance:The gas boiler is powered on, press start, the motor does not turn. Answer: Fault reason:1. Insufficient pneumatic locking.2. The solenoid valve is not sealing, and there is air leakage at the joint. Check the lock.3. The thermal relay is open.4. At least one of the conditional circuits is not valid (water level, pressure, temperature and to check whether the program controller is energized to start). Troubleshooting:1. Adjust the air pressure to the requested value.2. Clean or repair solenoid valve pipe joint.3. Check whether the component is damaged and motor current by reset.4. Check whether the water level, pressure and temperature exceed the limit.ZOZEN gas-fired boiler adopts automatic control to control the operation, combustion, water level, temperature and steam pressure. In case of such problems, the system will automatically prompt the error code.
  • What is the relationship between the boiler's flue gas volume and temperature? 2023-09-22
    The relationship between a boiler's flue gas volume and temperature is a complex interplay of various factors that depend on the boiler's design, type of fuel used, combustion efficiency, and operational settings. However, some general principles can help elucidate the relationship:   Combustion Efficiency: In an ideal combustion scenario, all the fuel would burn completely, generating water vapor and carbon dioxide primarily. However, real-world combustion is rarely perfect. Incomplete c...
  • How to estimate thermal efficiency of gas fired boilers? 2023-06-09
    There are several ways to estimate the thermal efficiency of gas-fired boilers:   1. Direct method: This method involves measuring the amount of fuel consumed and the amount of heat produced by the boiler. By comparing these two values, it is possible to calculate the thermal efficiency of the boiler.   2. Indirect method: The indirect method involves measuring various parameters such as flue gas temperature, ambient air temperature, and fuel consumption, and then calculating the t...
  • What fuels can be used in gas boilers? 2023-05-19
    Gas-fired boilers use gaseous flammable gases (including liquefied combustible gases) as fuel. These gaseous fuels have relatively higher calorific value and less pollutant emissions, and are gradually becoming popular among corporate users.
  • Why do nitrogen oxides form in boiler flue gas? 2023-04-07
    Boilers are widely used in various industries and households to provide heat or power. However, the combustion of fuel in the boiler chamber generates not only heat and steam, but also various pollutants, including nitrogen oxides (NOx). NOx is a group of harmful gases that can cause acid rain, smog, and respiratory diseases. Therefore, controlling the emission of NOx from boilers is crucial for both environmental protection and human health. The formation of NOx in boiler flue gas is a complex...
  • How to install FD fan, ID fan and flue gas dust in the gas-fired boiler system? 2022-12-02
    1. After boiler body, economizer, air pre-heater, dust collector, etc are in place and installed, connect FD fan, ID fan, etc according to drawing and then connect corresponding flue gas duct. After fan in place, alignment between foundation and equipment base should be conducted with parallels. Fan position alignment should center on a shaft, central elevation deviation and vertical and lateral central line positional deviation should be 10mm or less and fan spindle should be in level state. Th...
  • What is the process of biomass boiler flue gas treatment? 2021-11-26
    The flue gas treatment of biomass boiler adopts the pretreatment and deep processing. The deep processing adopts the pulsed jet cloth filter, the waste gas treated by this system can meet the discharge standard stably. The flue gas enters the cyclone dust collector or flame arrestor through the dust removal pipeline.
1 2 3 4 5 6 7 8...12