  • Can a fire tube boiler react quickly to load changes? 2024-04-26
    A firetube boiler can react very quickly to load changes due to the fact that it has a large volume of stored energy in the form of hot water and steam.
  • What applications do steam boilers have in the pharmaceutical industry? 2024-04-26
    The pharmaceutical sector is an area that requires the highest quality steam for its processes, known as clean steam, instead of other industrial steams. Some processes in this sector even need the highest level of quality - pure steam, which involves even stricter steam purity requirements for use in the sterilization of raw materials and pharmaceutical products at high temperatures.
  • What is the purpose to adjust the solid slagging of the pulverized coal furnace? 2024-02-16
    (1)Ensure normal and stable steam pressure, steam temperature and evaporation. (2)Avoid coking and burner damage; Ensure the safety of the operation of the superheater; Reduce pollution of combustion. (3)Make the operation achieve the highest economy.
  • What is the thermal efficiency of an industrial boiler? 2024-02-09
    The thermal efficiency of an industrial boiler is a measure of how effectively the boiler converts the energy contained in the fuel into usable heat. It is typically expressed as a percentage, indicating the ratio of heat output for heating or producing steam to the energy input from the fuel consumed. This efficiency is crucial for understanding the performance of a boiler, as it directly impacts fuel consumption, operational costs, and environmental emissions. Factors Influencing Thermal Effi...
  • Why doesn't the gas boiler's motor turn on after pressing the start button? 2023-11-24
    (Question details) specific performance:The gas boiler is powered on, press start, the motor does not turn. Answer: Fault reason:1. Insufficient pneumatic locking.2. The solenoid valve is not sealing, and there is air leakage at the joint. Check the lock.3. The thermal relay is open.4. At least one of the conditional circuits is not valid (water level, pressure, temperature and to check whether the program controller is energized to start). Troubleshooting:1. Adjust the air pressure to the requested value.2. Clean or repair solenoid valve pipe joint.3. Check whether the component is damaged and motor current by reset.4. Check whether the water level, pressure and temperature exceed the limit.ZOZEN gas-fired boiler adopts automatic control to control the operation, combustion, water level, temperature and steam pressure. In case of such problems, the system will automatically prompt the error code.
  • What are the causes of and solutions to false water level in steam boiler? 2023-04-27
    The water level of steam drum can reflect the condition between feedwater quantity and evaporation quantity of boiler. If the two parameters maintain a stable balance, the water level also remains unchanged; otherwise, the water level will rise or fall. Besides, there is also a false water level phenomenon. How do we understand the false water level?
  • What are the interlocks for a steam boiler? 2022-12-23
    An Interlock in the boiler’s control system is a programmed or hardwired condition that forces a device to be in a pre-determined or permissive state before the process can continue. Depending on design pressure, fuel type, either liquid, gas or solid, all steam boiler require interlocks to sequence the operation and to prevent damage to the boiler. Examples of such devices are High or Low Boiler Drum Water Level, Low Boiler Feed Pump Pressure, High or Low Fuel pressure, High or Low Atomization pressure (oil fired), Proof of Ignition, Proof of Flame, FD and/or ID (solid fuel) Fan Motor Operation or combustion air pressure, Damper or Valve position and High Boiler Steam Pressure as well as O2 and furnace temperature.
  • What are the functions of boiler auxiliaries? 2022-09-16
    Boiler heating can not be completed by only one boiler. It needs boiler auxiliaries such as combustion equipment, energy-saving equipment, water treatment system, fans and valves to form a complete heating system. So what is the function of boiler auxiliaries?   The role of boiler auxiliary Oil-fired gas burner: responsible for mixing fuel and oxygen in the boiler hearth, igniting through the ignition device, and continuously burning and heating the water inside the boiler;   Grat...